SOLAR APPLICATIONS 

13.1.

 

Night cooling 

 

Due  to  the  fact  that  in  solar  thermal 
schemes 

C

F

I

  there  is  no  risk  of 

reservoir  overheating  and  that  other 
protection  means  are  provided  for 
them against overheating, the function 
of  night  cooling  is  not  available  in 
these schemes. 

 

For correct operation of night cooling it 
is required that the clock is set. 

Night  cooling  function  is  used  to  cool 

DHW

  reservoir  by  emitting  excess  heat  through 

cold collector. It is done by starting the collector 
pump. 

During  night  cooling,  any  alternative 

sources of energy will be switched off. 

There  are  three  settings  for  night  cooling 

function:

  Night  cooling,  Night  cooling  ON, 

Night  cooling  OFF

  and  they  are  in

  Adjustment 

menu. 

Night cooling- YES: 

switches on, 

NO:

  switches 

off  the  night  cooling  mode.  When  the  mode 
is  on,  the  controller,  in  hours  0

00

÷5

00

,  if 

T2

 

sensor  temperature  is  higher  than  specified 
in 

Night  cooling  ON 

setting;  will  decide  to 

start  night  cooling.  The  controller  will  start 
the  collector  pump  in  order  to  discharge  to 
reservoir and will be cooling the reservoir to 
reach  temperature  specified  in 

Night 

cooling  OFF 

setting.  In  this  mode,  the 

controller  additionally  monitors  the  collector 
temperature;  cooling  will  be  stopped  for 
some  time,  if 

T1+dToff>T2

.  Regardless 

prior  conditions,  the  controller  will  exit  from 
the cooling mode at 5

00

 and return to normal 

operation. Activation of night cooling mode is 
indicated in the screen as blinking moon icon 
near the collector picture. 

Night cooling ON - 

DHW reservoir temperature 

(measured  by 

T2

),  when  reached,  if  night 

cooling  function  is  enabled  (prior  item) 
0

00

÷5

00

 and the temperature at 

T2

 sensor is 

higher than 

Night cooling ON 

temperature

,

 

the  controller  will  decide  on  night  cooling 
activation.  The  controller  will  start  the 
collector pump to discharge the reservoir and 
it  will  continue  to  cool  the  reservoir  to  the 
temperature set for 

Night cooling OFF

.  

Night 

cooling 

OFF 

DHW

 

reservoir 

temperature  (

T2 

sensor),  to  which  the 

controller will be cooling the reservoir during 
night cooling function. When the temperature 
drops to the one specified for 

Night cooling 

OFF

,

 

the controller will stop night cooling. 

 

Additionally,  depending  on  selected  scheme, 

the  controller  will  control  additional  outputs,  so 
as to discharge heat more efficiently. 

 

In scheme B

 during night cooling, circulation on 

output 

P2

 will be activated (regardless any time 

programs  etc.);  heater  operation  will  stopped 
(output

  H 

is  turned  off,  regardless  any  time 

programs etc.). 

In  schemes  D,  E,  G,  J,  K

  during  night  cooling, 

circulation  on  output

  H 

will  be  activated 

(regardless any time programs etc.). 

13.2.

 

Solar thermal scheme A  

Loading  of 

DHW

  reservoir  with  solar 

collector. 
 
This basic solar application.   

 

 

Fig. 13.1 Solar thermal scheme A 

The  collector  pump  will  be  started  with 

100% capacity, when difference between 

T1

 and 

T2

 

exceeds 

value 

of 

dTonDHW  

setting  and  it  will  be  working  for  the  time 
specified  in 

tP 

setting.  If  upon  this  time  the 

difference  between 

T1

  and 

T2

  is  still  above 

dTonDHW,

  the  pump  speed  will  remain  at 

100%. If the temperature difference between 

T1

 

and 

T2

  drops  below 

dTonDHW,

  the  controller 

will  start  reducing  the  pump  speed,  until  the 
moment  when 

T1

  and 

T2

  difference  reaches 

value specified in   

dToffDHW 

setting. When 

T1

 

and 

T2

  difference  is  between  the  values 

dTonDHW

  ÷ 

dToffDHW

,  the  controller  will 

calculate and set the pump speed proportionally. 
When 

dToffDHW

 is reached, the pump will work 

at minimal speed (parameter 

Pmin

), below it will 

be stopped. 

System  will  work  by  the  time  when 

T2

 

sensor  preset  temperature 

TsDHW 

is  reached, 

than the collector pump 

P1 

is stopped. 

If  the  collector  temperature 

T1

  reaches 

critical value (

TCOLcr 

parameter), the controller 

will allow the collector pump to be switched on to 
lower  the  collector  temperature  below 

HP1 

hysteresis parameter. 

If the reservoir temperature on 

T2

 sensor 

reaches  the  value  of 

TDHWmax,

  than  the 

controller, despite critical collector’s temperature 
(

TCOLcr

), will stop the collector pump, disabling 

the collector cooling. It is to protect the reservoir 
from overheating. 
 

Содержание PCSol 300

Страница 1: ...CLOCK CLOCK SUSTAIN TEMPORARY POWER HEAD OUTPUT ANTI FREEZING GRAPHIC DISPLAY POOL TANK PROTECTION HEATER SUPPORT PROGRAM HEATER PUMP ROTATION CONTROL NIGHT COOLING HEAT DISCHARGE VACUUM COLLECTOR 10...

Страница 2: ......

Страница 3: ...E SOLAR CIRCUIT SYSTEM 25 15 3 USER PARAMETERS 26 15 4 SERVICE PARAMETERS 26 15 5 HEAT YIELD GRAPH 27 15 6 NETWORK SETTINGS 27 INSTALLATION MANUAL 29 16 TECHNICAL DATA 30 16 1 ELEMENTS OF THE SET 30 1...

Страница 4: ...person who read and understood this manual Use only in heating systems that are set up in accordance with valid regulations Electric system to which the controller is connected must be protected with...

Страница 5: ...with the above crossed bin symbol it means that it meets requirements of the European Directive 2002 96 EC It is recommended to know your local electric and electronic products disposal system It is r...

Страница 6: ......

Страница 7: ...OPERATING MANUAL PCSol 300...

Страница 8: ...e during controller operation when you keep the encoder pressed for 3 seconds it will cause exit to the main screen All controller settings are made through menu system MENU is recalled by pressing en...

Страница 9: ...The changed value will be confirmed when you press the knob again and you may select other setting After edition in submenu you may select the following by pressing on selection OK Confirms changes a...

Страница 10: ...hich the controller controls H output heater or other additional heat source When you switch off the temperature value in value edition box the time program will be set off and the controller will use...

Страница 11: ...disable circulation Value sch will activate time program for circulation 9 MENU ALARMS Access The controller may alarm on any irregularities in operation The controller has an intelligent alarm functi...

Страница 12: ...algorithm stops DHW reservoir loading 6 T3 sensor malfunction Alarm informs on incorrect operation or damage to T3 sensor Check connections for continuity connect or short circuit eliminate in sensor...

Страница 13: ...ed description of the options parameters is included in installation part of the manual Password 0000 will display submenu parameters only for reading 10 1 Restoring factory settings This menu allows...

Страница 14: ...rned off when Time Out has elapsed This function is useful to find the controller in dark rooms Encoder knob light pulsation will be also performed after the controller is switched off 11 2 Operation...

Страница 15: ...nu will not display heat output icon and the function may not be entered The controller logs data on recovered energy from last 14 days in the form of bar chart Fig 12 1 Heat output screen Energy tota...

Страница 16: ...DHW reservoir temperature T2 sensor to which the controller will be cooling the reservoir during night cooling function When the temperature drops to the one specified for Night cooling OFF the contro...

Страница 17: ...p to the temperature of TDHWmin Functioning of H output depends also on eco function set up as described in Adjustment menu TDHWmin temperature is set through main menu item TDHWmin List of settings i...

Страница 18: ...art reducing the pump speed until the difference between T1 and T2 reaches the value specified as dToffDHW If the difference between T1 and T2 is between the values dTonDHW dToffDHW the controller wil...

Страница 19: ...ture preset of hysteresis respectively HP1 for P1 pump and HP2 for P2 pump Eventually when the temperature at the collector sensor T1 will reach critical value TCOLcr Then the controller will allow sw...

Страница 20: ...t affect the controller operation If the parameter is set as NO the controller will not alarm when TCOLcr temperature is exceeded at the collector sensor 13 8 Solar thermal scheme G Loading of DHW res...

Страница 21: ...reaches the value specified as dToffDHW If the difference between T3 and T2 is between the values dTonDHW dToffDHW the controller will calculate and set the pump speed proportionally When dToffDHW is...

Страница 22: ...said difference between T1 and T2 drops below dTonDHW the controller will start reducing the pump speed until the difference between T1 and T2 reaches the value specified as dToffDHW If the differenc...

Страница 23: ...temperature on T2 sensor to which the regulator will be cooling down the container if night cooling function is enabled and Cooling temp ON temperature is exceeded between 000 500 TCOLkr alarm Enabli...

Страница 24: ...ff night cooling mode active from 0000 0500 Night cooling ON temperature of DHW tank read out of T2 sensor upon excess of which the regulator will activate night cooling mode at 000 provided that nigh...

Страница 25: ...over a Wi fi or LAN network The interface is operated by an ordinary search engine installed in any stationary and mobile communication devices 15 1 Basic data reading Fig 15 1 WWW interface tiles 15...

Страница 26: ...26 15 3 User parameters Fig 15 3 WWW interface user parameters 15 4 Service parameters Fig 15 4 WWW interface service parameters...

Страница 27: ...27 15 5 Heat yield graph Fig 15 5 WWW interface heat yield graph 15 6 Network settings Fig 15 6 WWW interface network settings screen...

Страница 28: ......

Страница 29: ...INSTALLATION MANUAL PCSol 300...

Страница 30: ...which heat output is not counted 17 INSTALLATION OF PCSol 300 The controller is designed for operation in the environment where only dry conductive contaminations may be present 2 degree of contamina...

Страница 31: ...rotection is ensured suitably to environmental conditions dust and water access is prevented permissible operating temperature is not exceeded for the controller 40 C air exchange inside casing is all...

Страница 32: ...cuits 0 75 1mm2 Low voltage circuits 0 25 0 75mm2 For installations with bare wire cables the maximal size is 1 5mm2 For good connection between the terminal and cable insulation and sleeve free lengt...

Страница 33: ...7 6 Connection of pumps Pump P2 is connected analogically as pump P1 Fig 17 7 Electro valve connection The connection shown in fig 17 7 requires electro valve coil adjusted to 230 voltage 17 2 3 Tempe...

Страница 34: ...sulating material so that there is sufficient temperature convection to the sensor Fig 17 9 Sensor installation on pipe surface 17 2 5 Output H connection Output H is adapted to connect relay supplied...

Страница 35: ...tion of rotations are connected via a relay and its contacts to relevant terminals Status relations on H outlet and respective direction of the valve switching are presented in application schemes Cha...

Страница 36: ...to the Internet in two ways over Wi fi to the local access point directly through Ethernet cable for LAN network The most convenient way of connection is recommended Both ways offer the same operation...

Страница 37: ...roller to count heat output install additional CT6 sensor on the outlet of lower pipe coil from DHW reservoir and connect to T4 input or T3 for Basic The sensor must be installed possibly near the con...

Страница 38: ...t will disable reservoir extra heating function How to connect H output to a heater via a relay is presented in details in section 17 2 5 Fig 18 2 Application scheme B Installation notes 1 For the con...

Страница 39: ...t The sensor must be installed possibly near the connector pipe 2 T3 sensor shows temperature in upper part of the reservoir its connection is not required 3 Circulation pump is connected to H output...

Страница 40: ...contact current not lower than the current of the circulation pump It is recommended to use relays with two switching tracks see details in section 17 2 5 Output H Setting notes 1 Do not set HP2 valu...

Страница 41: ...t 2 Circulation pump is connected to H output through a relay with contact current not lower than the current of the circulation pump It is recommended to use relays with two switching tracks see deta...

Страница 42: ...s near zero switching time set minimal value for tVALVE 3 When the circuits are being switched tVALVE time the collector pump is not working and the circuit receives no heat Pay attention to collector...

Страница 43: ...boiler Fig 18 7 Application scheme G Installation notes 1 Circulation pump is connected to H output through a relay with contact current not lower than the current of the circulation pump It is recomm...

Страница 44: ...troller to count heat output install additional CT6 sensor on DHW reservoir lower pipe coil and connect it to T4 input The sensor must be installed possibly near the connector pipe 3 Circulation pump...

Страница 45: ...losses incurred in the collector exchanger section will prevent starting of P2 pump even at high temperatures in the collector This setting must be selected specifically to each installation 3 During...

Страница 46: ...it is required to install additional CT6 sensor directly on the return from the DHW reservoir lower pipe coil and connect it to T4 measurement input 2 Circulation pump is connected to H output throug...

Страница 47: ...instructions 1 Two additional CT6 sensors are required for the application schema 2 Connect the circulation pump to H output via a transmitter with connector voltage not lower than circulation pump v...

Страница 48: ...enable calculation of heat yield by the regulator install additional CT6 type sensor at the outlet of lower pipe coil from DHW tank and connect it to T4 input The sensor should be mounted as close as...

Страница 49: ...a service password Fig 20 1 User login screen To login place cursor in selected digit by its rotating then press the button When the digit is blinking rotate the encoder to change its value Confirm t...

Страница 50: ...ical temperature Temperature which regardless of reaching reservoir preset TsDHW or pool preset TsPOOL will start the collector pump at 100 capacity in order to discharge heat from the collector It wi...

Страница 51: ...atically move sensor s characteristics to compensate the effect of additional resistance When you enter menu the controller displays current values of temperature corrections If the controller display...

Страница 52: ...collector function on off The function principle of operation is described in section 20 3 1 Detect level setting that defines how much the collector temperature must rise at started vacuum collector...

Страница 53: ...used as per IEC 60127 standard An example of a fuse meeting the requirements is Schurter MXT 250 time delay fuse To replace open controller s enclosure and replace burnt fuse with a new one Fig 21 1...

Страница 54: ......

Страница 55: ......

Страница 56: ...SALUS Controls ul Bielska 4a 43 200 Pszczyna Poland...

Отзывы: