tP – 

Minimal time of the collector pump work. If 

the  difference  between  collector  and 
reservoir  temperatures  drops  to 

dTon

,  the 

collector pump will be started for the time of 

tP

HP1

- auxiliary hysteresis for 

P1 

output. 

HP2 

- auxiliary hysteresis for 

P2 

output. 

 

 

Too  high  values  of 

HP1

HP2

  settings 

may  lead  to  large  temperature 
oscillations  in  the  system,  so  it  is 
recommended  to  leave  them  at  the 
level of 1°C. 
 

tVALVE  – 

minimal  operation  time  of  the 

controller’s  valve  that  switches  the  circuits 
(used in solar application 

F

). 

tDLY  – 

time  of  delay  for  switching  on/off  the 

pump downstream heat exchanger.  

TCOmin 

–  minimal  temperature  in 

CH

  circuit 

(measured  by 

T4 

sensor)  in  scheme 

G,

 

which  allows  loading  of  DHW  reservoir  from 
the  boiler  system.  Below  this  temperature 
(even  if  there  are  conditions  for  reservoir 
loading,  i.e. 

TsDHW

  is  lower  than  preset  or 

dTCO 

is  reached),  the  controller  will  disable 

the  reservoir  loading.  This  prevents 

CH 

circuit operation below the boiler’s dew point. 

dTP2 

–  temperature  difference  between 

T1

 

collector  and 

T4 

exchanger,  if  reached  the 

controller  will  start  exchanger  pump  in 
scheme 

I

.  Operation  with 

tDLY

  is  also 

possible,  then 

dTP2

  setting  must  set  as 

OFF

.  At  such  setting,  the  controller  will  run 

P2

 operational algorithm with delay of 

tDLY

 

in relation to 

P1 

pump operation. Alarm from 

T4

 sensor will not be reported. 

20.2.

 

I\O Options\Configuration 

Depending  on  the  length  of  sensor  extension 

cable,  sensors  will  show  temperature  without 
taking  into  account  resistance  of  connection 
lines. To compensate cable effects, it is required 
to perform sensor compensation procedure. 

20.2.1.

 

Wire length compensation 

 

It  consists  in  measurement  of  wires 

connected  to  a  sensor  (measurement  track), 
reading  value  from  the  compensation  table  for 
connecting  wire  resistance,  and  programming 
this value in the controller.  
The  controller  will  automatically  move  sensor’s 
characteristics  to  compensate  the  effect  of 
additional resistance. 

When  you  enter  menu,  the  controller 

displays 

current 

values 

of 

temperature 

corrections.  
If  the  controller  displays  0.0,  it  means  that  no 
correction  has  been  introduced  for  given  track. 

To  clear  any  compensation  data  for  the  track, 
enter 0.0 value.  

The  procedure  may  be  conducted  using 

ohmmeter  to  measure  resistance  of  both  cable 
conductors  and  selecting  from  the  table 
respective value for measured resistance. 
If received result indicates correction above 2°C, 
it  may  means  that  the  cable  have  resistance 
bigger than permissible or that they are too long. 
 

Table of cable lengths and resistance. 

           size 
length 

0,5mm

2

  0,75mm

2

 

1mm

2

 

5m 

0,35Ω 

0,1°C 

0,23Ω 

0,1°C

 

0,18Ω 

0,1°C

 

10m 

0,69Ω 

0,2°C

 

0,46Ω 

0,2°C

 

0,35Ω 

0,1°C

 

15m 

1,04Ω 

0,3°C

 

0,69Ω 

0,2°C

 

0,52Ω 

0,2°C

 

20m 

1,38Ω 

0,4°C

 

0,92Ω 

0,3°C

 

0,69Ω 

0,2°C

 

25m 

1,73Ω 

0,5°C

 

1,15Ω 

0,3°C

 

0,87Ω 

0,3°C

 

30m 

2,07Ω 

0,6°C

 

1,38Ω 

0,4°C

 

1,04 Ω 

0,3°C

 

20.3.

 

Options\Functions 

Depending on scheme and version, the following 
settings are available in the Functions menu: 

Setting 

Scheme 

A  B  C  D  E  F  G  H  I  J  K  L 

Antifreeze 

X  X  X  X  X  X  X  X  X  X  X  X 

Work fluid 

X  X  X  X  X  X  X  X  X  X  X  X 

Flow P1 

X  X  X  X  X  X  X  X  X  X  X  X 

Flow P2 

              X         

Vac. collector 

X  X  X  X  X  X  X  X  X  X  X  X 

Detect. level 

X  X  X  X  X  X  X  X  X  X  X  X 

Operation time 

X  X  X  X  X  X  X  X  X  X  X  X 

 

Antifreeze  – 

setting 

ON

  enables  the  antifreeze 

function.  The  collector  pump  will  be  started, 
if  the  solar  work  fluid  temperature  drops  to 
the freezing value set for the work fluid. For 
correct  operation  of  this  function,  it  is 
required  to  select  suitable  solar  work  fluid. 
Collector  pump  will  be  stopped,  if  the  work 
fluid  temperature  rises  by  2°C.  When  the 
function is off, the controller will not monitor 
antifreeze and it may lead to damage of the 
solar  system  in  winter  period,  so  it  is 
recommended that it remains on. In scheme 
E,  antifreeze  function  operates  in  the  circuit 
of  reservoir  A,  in  scheme  F  the  function 
operates  in  priority  circuit.  If  in  the  system 
with 

DHW

 

reservoir 

the 

reservoir 

temperature  drops  down  to  2°C,  the 

Содержание PCSol 300

Страница 1: ...CLOCK CLOCK SUSTAIN TEMPORARY POWER HEAD OUTPUT ANTI FREEZING GRAPHIC DISPLAY POOL TANK PROTECTION HEATER SUPPORT PROGRAM HEATER PUMP ROTATION CONTROL NIGHT COOLING HEAT DISCHARGE VACUUM COLLECTOR 10...

Страница 2: ......

Страница 3: ...E SOLAR CIRCUIT SYSTEM 25 15 3 USER PARAMETERS 26 15 4 SERVICE PARAMETERS 26 15 5 HEAT YIELD GRAPH 27 15 6 NETWORK SETTINGS 27 INSTALLATION MANUAL 29 16 TECHNICAL DATA 30 16 1 ELEMENTS OF THE SET 30 1...

Страница 4: ...person who read and understood this manual Use only in heating systems that are set up in accordance with valid regulations Electric system to which the controller is connected must be protected with...

Страница 5: ...with the above crossed bin symbol it means that it meets requirements of the European Directive 2002 96 EC It is recommended to know your local electric and electronic products disposal system It is r...

Страница 6: ......

Страница 7: ...OPERATING MANUAL PCSol 300...

Страница 8: ...e during controller operation when you keep the encoder pressed for 3 seconds it will cause exit to the main screen All controller settings are made through menu system MENU is recalled by pressing en...

Страница 9: ...The changed value will be confirmed when you press the knob again and you may select other setting After edition in submenu you may select the following by pressing on selection OK Confirms changes a...

Страница 10: ...hich the controller controls H output heater or other additional heat source When you switch off the temperature value in value edition box the time program will be set off and the controller will use...

Страница 11: ...disable circulation Value sch will activate time program for circulation 9 MENU ALARMS Access The controller may alarm on any irregularities in operation The controller has an intelligent alarm functi...

Страница 12: ...algorithm stops DHW reservoir loading 6 T3 sensor malfunction Alarm informs on incorrect operation or damage to T3 sensor Check connections for continuity connect or short circuit eliminate in sensor...

Страница 13: ...ed description of the options parameters is included in installation part of the manual Password 0000 will display submenu parameters only for reading 10 1 Restoring factory settings This menu allows...

Страница 14: ...rned off when Time Out has elapsed This function is useful to find the controller in dark rooms Encoder knob light pulsation will be also performed after the controller is switched off 11 2 Operation...

Страница 15: ...nu will not display heat output icon and the function may not be entered The controller logs data on recovered energy from last 14 days in the form of bar chart Fig 12 1 Heat output screen Energy tota...

Страница 16: ...DHW reservoir temperature T2 sensor to which the controller will be cooling the reservoir during night cooling function When the temperature drops to the one specified for Night cooling OFF the contro...

Страница 17: ...p to the temperature of TDHWmin Functioning of H output depends also on eco function set up as described in Adjustment menu TDHWmin temperature is set through main menu item TDHWmin List of settings i...

Страница 18: ...art reducing the pump speed until the difference between T1 and T2 reaches the value specified as dToffDHW If the difference between T1 and T2 is between the values dTonDHW dToffDHW the controller wil...

Страница 19: ...ture preset of hysteresis respectively HP1 for P1 pump and HP2 for P2 pump Eventually when the temperature at the collector sensor T1 will reach critical value TCOLcr Then the controller will allow sw...

Страница 20: ...t affect the controller operation If the parameter is set as NO the controller will not alarm when TCOLcr temperature is exceeded at the collector sensor 13 8 Solar thermal scheme G Loading of DHW res...

Страница 21: ...reaches the value specified as dToffDHW If the difference between T3 and T2 is between the values dTonDHW dToffDHW the controller will calculate and set the pump speed proportionally When dToffDHW is...

Страница 22: ...said difference between T1 and T2 drops below dTonDHW the controller will start reducing the pump speed until the difference between T1 and T2 reaches the value specified as dToffDHW If the differenc...

Страница 23: ...temperature on T2 sensor to which the regulator will be cooling down the container if night cooling function is enabled and Cooling temp ON temperature is exceeded between 000 500 TCOLkr alarm Enabli...

Страница 24: ...ff night cooling mode active from 0000 0500 Night cooling ON temperature of DHW tank read out of T2 sensor upon excess of which the regulator will activate night cooling mode at 000 provided that nigh...

Страница 25: ...over a Wi fi or LAN network The interface is operated by an ordinary search engine installed in any stationary and mobile communication devices 15 1 Basic data reading Fig 15 1 WWW interface tiles 15...

Страница 26: ...26 15 3 User parameters Fig 15 3 WWW interface user parameters 15 4 Service parameters Fig 15 4 WWW interface service parameters...

Страница 27: ...27 15 5 Heat yield graph Fig 15 5 WWW interface heat yield graph 15 6 Network settings Fig 15 6 WWW interface network settings screen...

Страница 28: ......

Страница 29: ...INSTALLATION MANUAL PCSol 300...

Страница 30: ...which heat output is not counted 17 INSTALLATION OF PCSol 300 The controller is designed for operation in the environment where only dry conductive contaminations may be present 2 degree of contamina...

Страница 31: ...rotection is ensured suitably to environmental conditions dust and water access is prevented permissible operating temperature is not exceeded for the controller 40 C air exchange inside casing is all...

Страница 32: ...cuits 0 75 1mm2 Low voltage circuits 0 25 0 75mm2 For installations with bare wire cables the maximal size is 1 5mm2 For good connection between the terminal and cable insulation and sleeve free lengt...

Страница 33: ...7 6 Connection of pumps Pump P2 is connected analogically as pump P1 Fig 17 7 Electro valve connection The connection shown in fig 17 7 requires electro valve coil adjusted to 230 voltage 17 2 3 Tempe...

Страница 34: ...sulating material so that there is sufficient temperature convection to the sensor Fig 17 9 Sensor installation on pipe surface 17 2 5 Output H connection Output H is adapted to connect relay supplied...

Страница 35: ...tion of rotations are connected via a relay and its contacts to relevant terminals Status relations on H outlet and respective direction of the valve switching are presented in application schemes Cha...

Страница 36: ...to the Internet in two ways over Wi fi to the local access point directly through Ethernet cable for LAN network The most convenient way of connection is recommended Both ways offer the same operation...

Страница 37: ...roller to count heat output install additional CT6 sensor on the outlet of lower pipe coil from DHW reservoir and connect to T4 input or T3 for Basic The sensor must be installed possibly near the con...

Страница 38: ...t will disable reservoir extra heating function How to connect H output to a heater via a relay is presented in details in section 17 2 5 Fig 18 2 Application scheme B Installation notes 1 For the con...

Страница 39: ...t The sensor must be installed possibly near the connector pipe 2 T3 sensor shows temperature in upper part of the reservoir its connection is not required 3 Circulation pump is connected to H output...

Страница 40: ...contact current not lower than the current of the circulation pump It is recommended to use relays with two switching tracks see details in section 17 2 5 Output H Setting notes 1 Do not set HP2 valu...

Страница 41: ...t 2 Circulation pump is connected to H output through a relay with contact current not lower than the current of the circulation pump It is recommended to use relays with two switching tracks see deta...

Страница 42: ...s near zero switching time set minimal value for tVALVE 3 When the circuits are being switched tVALVE time the collector pump is not working and the circuit receives no heat Pay attention to collector...

Страница 43: ...boiler Fig 18 7 Application scheme G Installation notes 1 Circulation pump is connected to H output through a relay with contact current not lower than the current of the circulation pump It is recomm...

Страница 44: ...troller to count heat output install additional CT6 sensor on DHW reservoir lower pipe coil and connect it to T4 input The sensor must be installed possibly near the connector pipe 3 Circulation pump...

Страница 45: ...losses incurred in the collector exchanger section will prevent starting of P2 pump even at high temperatures in the collector This setting must be selected specifically to each installation 3 During...

Страница 46: ...it is required to install additional CT6 sensor directly on the return from the DHW reservoir lower pipe coil and connect it to T4 measurement input 2 Circulation pump is connected to H output throug...

Страница 47: ...instructions 1 Two additional CT6 sensors are required for the application schema 2 Connect the circulation pump to H output via a transmitter with connector voltage not lower than circulation pump v...

Страница 48: ...enable calculation of heat yield by the regulator install additional CT6 type sensor at the outlet of lower pipe coil from DHW tank and connect it to T4 input The sensor should be mounted as close as...

Страница 49: ...a service password Fig 20 1 User login screen To login place cursor in selected digit by its rotating then press the button When the digit is blinking rotate the encoder to change its value Confirm t...

Страница 50: ...ical temperature Temperature which regardless of reaching reservoir preset TsDHW or pool preset TsPOOL will start the collector pump at 100 capacity in order to discharge heat from the collector It wi...

Страница 51: ...atically move sensor s characteristics to compensate the effect of additional resistance When you enter menu the controller displays current values of temperature corrections If the controller display...

Страница 52: ...collector function on off The function principle of operation is described in section 20 3 1 Detect level setting that defines how much the collector temperature must rise at started vacuum collector...

Страница 53: ...used as per IEC 60127 standard An example of a fuse meeting the requirements is Schurter MXT 250 time delay fuse To replace open controller s enclosure and replace burnt fuse with a new one Fig 21 1...

Страница 54: ......

Страница 55: ......

Страница 56: ...SALUS Controls ul Bielska 4a 43 200 Pszczyna Poland...

Отзывы: