47
7.3.5. RS-485 interface parameters.
•
The parameters relating to communication through the
RS-485 interface can be configured through the RS-
485 MODBUS menu. This menu allows you to configure
the MODBUS address, communication mode and data
transmission speed.
7.3.6. Battery setting.
7.3.6.1. Installing a new battery.
The INSTALL NEW BATT. menu is used if the BCB switch has
not been closed when requested in the startup phase. In this
case, the system will start considering the battery to be fully
discharged, activating alarm A10 (battery failure).
To configure the battery backup to 100%, it is necessary to
access the menu and confirm the operation on the confirmation
screen.
7.3.6.2. Battery configuration.
If the UPS has been tested without knowing the characteristics
of the batteries, the BATTERY SETTING menu enables that
data to be configured. In particular, the following data can be
configured:
Battery capacity in ampere hours (Ah)
Recharge current in amperes (A)
Rated autonomy in minutes
Fig. 68.
Battery parameter configuration.
The various parameter configuration pages are similar and
require the operator to enter and confirm the value.
Fig. 69.
Battery parameters setting example.
7.3.6.3. Battery test.
The BATTERY TEST menu allows you to perform a short battery
discharge test. If the batteries are not efficient, alarm A10
(Battery failure) is activated at the end of the test.
Possible loss of power.
This test can affect the continuity of the supply to the
loads if the batteries are not fully charged.
7.3.7. UPS test.
The UPS TEST enables an inverter switching test to be carried
out. The inverter shuts down and the load is transferred to the
bypass. The power of the inverter will automatically reset after
a few seconds.
Possible loss of power.
In case of power failure while performing this test, the
immediate operation of the inverter is not guaranteed.
7.3.8. Network parameter configuration.
The NETWORK CONFIGURATION menu enables configuration
of network parameters and the system clock synchronisation
server.
All of the parameters that can be set in this section relate to the
communication ports (LAN and RS-485) available on the same
touch screen.
Fig. 70.
Configuration of the network parameters on the
touch screen.
7.3.8.1. Configuration of the LAN parameters.
The LAN parameters that can be configured are the following:
IP address.
Network mask.
Network gateway.
Primary DNS server.
Secondary DNS server.
Enable/disable DHCP.
X-PERT
UNINTERRUPTIBLE POWER SUPPLIES (UPS)
USER MANUAL
Содержание SLC X-PERT Series
Страница 1: ...SLC X PERT 80 400 kVA UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...
Страница 8: ...8 SALICRU Fig 3 Front view of the 400 kVA model...
Страница 18: ...18 SALICRU 880 1978 947 Air outlet openings Front air inlet openings Fig 16 Dimensions of 200 300 kVA devices...
Страница 34: ...34 SALICRU Fig 42 Connection of three UPSs through the CAN bus for 400 kVA devices...
Страница 60: ...60 SALICRU...
Страница 61: ...61 X PERT UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...