9. ANNEXES.
9.1. GENERAL TECHNICAL SPECIFICATIONS.
Model
SLC X-PERT
Power (kVA)
80
100
125
160
200
250
300
400
Active power (kW)
80
100
125
160
200
250
300
400
GENERAL
UPS type
On-line double-conversion
Efficiency (%)
(VFI: on-line double-conversion)
25% load
93.0
93.0
93.0
93.0
94.5
94.5
94.5
>94.8
50% load
94.5
94.5
94.5
94.5
95.5
95.5
95.8
96.0
75% load
95.0
95.0
95.0
95.0
96.0
96.0
96.0
>96.0
100% load
95.0
95.0
95.0
95.0
≥
95.5
95.5
95.5
>95.8
Efficiency (%)
(VFD ECO MODE) load ≥50%
≥
98.0
Losses with rated load (kW)
4.2
5.3
6.6
8.4
9.4
11.8
14.1
17.5
Ambient eorking temperature (°C)
UPS
Battery
0... 40
0... 25
Storage temperature (°C)
UPS
Battery
-10... 70
-10... 60
-10... 70
-15... 40
Relative humidity, non-condensing (%)
<95
Maximum working altitude (m)
<2400 masl
Ventilation
Forced
Cooling air flow (m
3
/h)
1000
1200
1200
1500
1800
2200
2300
4000
Noise (dB)
<60
<65
<72
No. battery cells (lead)
360... 372
Protection rating
IP20
Electromagnetic compatibility
EN-IEC 62040-2 (CE marking)
Safety
EN-IEC 62040-1
Operation and test
EN-IEC 62040-3
Quality and Environment
ISO 9001 – ISO 14001
Colour
RAL 9005
Accessibility
Front and side access
Front access
Installation
Against the wall
Overall dimensions (mm)
Depth
940
970
970
Width
560
880
1450
High
1800
1978
1978
Weight (without batteries) (kg)
300
320
360
380
720
850
900
1080
Weight (with batteries) (kg)
850
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Input/output terminals
Input cables from below
Handling
Base for forklift
Storage and transportation conditions
According to EN 62040-3
Front panel
10” touch screen
Potential-free contacts interface
Optional for signalling/alarms
Serial communication interface
Standard: RS-232/USB
Optional: RS-485 (MODBUS RTU protocol)
Parallel configuration (optional)
Up to 5+1 (redundant parallel)
Up to 6 (parallel with power)
(1)
RECTIFIER AND BATTERY CHARGER
Input
3 phases/4 wires
Three-phase rated input voltage (Vac)
3x400
Tolerance (%)
-20... +15
Содержание SLC X-PERT Series
Страница 1: ...SLC X PERT 80 400 kVA UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...
Страница 8: ...8 SALICRU Fig 3 Front view of the 400 kVA model...
Страница 18: ...18 SALICRU 880 1978 947 Air outlet openings Front air inlet openings Fig 16 Dimensions of 200 300 kVA devices...
Страница 34: ...34 SALICRU Fig 42 Connection of three UPSs through the CAN bus for 400 kVA devices...
Страница 60: ...60 SALICRU...
Страница 61: ...61 X PERT UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...