Check the control board
Error 36
Outdoor unit Low pressure switch trip
The pressure of refrigerant in the system is lower
than the limit.
Does refrigerant shortage
or clogging
Fix refrigerant problem
Are all indoor unit EXV
work normal?
Check indoor unit EXV
Is low pressure switch
work normal ?
Check Low pressure switch
Check code
Check code name
cause