Check the control board
Error 16
Outdoor unit Mid Coil Temperature
sensor fail
There is an error in the refrigerant temperatre
sensor at a middle of heat sink coil.
Is sensor connect on
control board ?
Correct connector connection
Is the wire of the sensor
normal ?
Change the sensor
Is sensor resistance
normal ?
Change the sensor
Check code
Check code name
cause