Is the coil resistance of the
compressor 2 normal ?
Change the compressor
Is operation of the
compressor 2 control
board normal ?
check control board
Chang the control board
Check code
Check code name
cause
Error 20
Compressor 2 Current sensor fail
There is an error in the dldctric current sensor of
compressor 2
Is the wiring between
compressor 2 and control board
of comoressor normal ?
Correct connection wiring
compressor and control board.