1. Press the SET button and hold 10 seconds until the screen shows the ID number.
2. Press the SET button and hold 5 seconds to save the setting and back to the home page.
TEST RUN
Before test run
Confirm that the valve of the refrigerate pipe of the outdoor unit is OPEN
Do not run the unit if it is less than 1 MΩ
Methods of test run
Operate the system normally of cold system to use the wired remote controller and hot system to
use board controller of master unit.
Operate the system by using the wired remote controller
1. Turning on the power
2. Press Mode button to operate in cool mode
3. Press Fan speed to operate in speed HiHi
4. Press Down button to operate in 15 C
Saijo denki International co.,ltd.
50
Before turning on the power, confirm that the resistance between the terminal block of power supply and the earth is
more than 1 M using a 500V megohmmeter.
When the remote controller is in setup ID status
Show 2 digits number
Show "A"
Содержание CVIA-80-CPF3