5 ADDRESS SETTING
! CAUTION
• Be sure to complete the electric wiring before setting the addresses.
• It may take up to ten minutes (normally about five minutes) to address one refrigerant line automatically.
• Running the unit is not required for address setting.
• The addresses can be set manually.
setting addresses using SW15 on the interface P.C. board on the header outdoor unit
setting addresses on the wired remote controller.
Process
1. Press Status On-screen will be shown "CONTROL"
Saijo denki International co.,ltd.
45
* When setting an address manually, the wired remote controller must temporarily be
paired with an indoor unit one-to-one. (when the system is organized for group operation
and no Remote controller)
On this unit, it is required to set the addresses of the indoor units before starting air conditioning. Set the addresses
following the steps below.
• If you turn on the outdoor unit before turning on the indoor units, the CODE No. [E19] is indicated on the 7- segment
display on the interface P.C. board of the outdoor unit until the indoor units are turned on. This is not a malfunction.
• Settings on the outdoor unit are required for automatic addressing. (Address setting is not started simply by turning
on the power.)
Automatic addressing:
Manual addressing:
LED Control
Status Button
Can set the address of the indoor unit in the system automatically via the control board in the outdoor unit that is the
master.