Code
Name
Description 1
Check Posltion
Description 2
SWV-09-A-VTGP1
SWV-13-A-VTGP1
SWV-20-A-VTGP1
SWV-25-A-VTGP1
SWV-30-A-VTGP1
SWV-36-A-VTGP1
01
-
-
-
-
-
-
-
-
-
- Check blockage at the drain pipe
-
-
-
-
-
-
- Check operating of the water pump
-
-
-
-
-
-
-
- Check operation of the float
-
-
-
-
-
-
-
- Check operation of the control board
Control board
- Check all connector sensor on control board
all position P1
-
-
-
-
-
-
- Check the wire of the sensor
- Check sensor resistance
- Check operation of the control board
Control board
- Check all connector sensor on control board
all position P2
-
-
-
-
-
-
- Check the wire of the sensor
- Check sensor resistance
- Check operation of the control board
Control board
- Check all connector sensor on control board
all position P3
-
-
-
-
-
-
- Check the wire of the sensor
- Check sensor resistance
- Check operation of the control board
Control board
- Check connector motor on control board
- Check operation of motor
Fan motor
- Check operation of the control board
Control board
Fan coil ass'y
6SP301ASHE031
6SP301ASHE035
6SP301ASHE026
6SP301ASHF034
Cross flow fan
6SP431G-0001402
6SP431G-00015 ( R )
6SP431G-00016 ( L )
- Check speed of fan motor
Fan motor
- Check the quantity of working fluid in the
system
08
-
-
-
-
-
-
-
-
09
-
-
-
-
-
-
-
-
10
-
-
-
-
-
-
-
-
Saijo denki International co.,ltd.
53
6SP505AMWB296DS01
6SP505AMWB296DS02
6SP505AMWB296DS03
6SP551A-00025
02
Indoor unit Flood Protection
There is an error in the drainage of
the indoor unit
03
Indoor unit Room Temperature sensor
fail
There is an error in room temperature
seneor at the cooler.
6SP505AMWB296DS01
6SP505AMWB296DS02
6SP505AMWB296DS03
6SP551A-00005
04
Indoor unit Inlet Temperature sensor fail
06
Indoor unit Motor fail
There is an error in the cooling motor
of the Indoor unit.
07
Indoor Antifreeze protection
There is freezing at cooling coil.
There is an error in the refrigerant
temperature sensor at the Evaporator
inlet.
05
Indoor unit Outlet Temperature sensor
fail
There is an error in the refrigerant
temperature sensor at the Evaporator
outlet.
8 ERROR CODE
6SP505AMWB296DS01
6SP505AMWB296DS02
6SP505AMWB296DS03
6SP511A-0004701
6SP511A-00049
6SP301ASHG013
6SP504CSHA031
6SP505AMWB296DS01
6SP505AMWB296DS02
6SP505AMWB296DS03
-
-
6SP511A-00049
6SP511A-0004701
6SP505AMWB296DS01
6SP505AMWB296DS02
6SP505AMWB296DS03
6SP431G-0001302
Control Ass'y
Defrost sensorR (105 cm.)
(Outlet)
Defrost sensor (60 cm.) (Inlet)
Room thermistor
- Check the coil and fan blades