Saia-Burgess
Controls Ltd.
Hardware Manual for the PCD3 Series│Document 26/789; Version E 5│31.01.2005
Hardware
PCD3.E160
5-10
5
5.2.2 PCD3.E160, 16 digital inputs, ribbon cable connector
Application
Economical input module for source or sink operation with 16 inputs, electrically
connected. Suitable for most electronic and electromechanical switch elements
applied to 24 VDC.
Technical data
Number of inputs:
16
electrically connected,
source or sink operation
Input voltage:
24 VDC smoothed or pulsed
Input current:
4 mA per input at 24 VDC
Typical input delay:
8 ms
Noise resistance:
acc. to IEC IEC 1000-4-4
2 kV under capacitive coupling (whole trunk group)
Internal current consumption:
(from +5 V bus)
1...10 mA
typ. 8 mA
Internal current consumption:
(from V+ bus)
0 mA
External current consumption max. 64 mA (all inputs = H) at 24 VDC
Terminal:
34-pole, standard ribbon cable connector
LED’s and connection terminals
Saia-Burgess Controls provides a broad range of pre-configured connection cables
with a 34 pole ribbon connector at one or both ends.
This connection cables can be plugged at one end into the PCD3.E160 I/O modules
and at the other end into a I/O terminal adapter.
The following adapters are obtainable from Saia-Burgess Controls: terminal adapters
for connecting 3-wire sensors to individual terminals for Signal, Plus and Minus;
terminal adapters for connecting 16 I/Os with and without LED and relay interface;
and terminal adapters with changeover contacts for signal conversion for digital
output modules.
For details, please refer to TI 26-326, “System cables”.
PCD3. E160
16 Iutputs 24VDC
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
–
–
–
–
L
L
L
L
–
–
–
–
L
L
L
L
E15
E8
E7
E0
L –
L –
E
n
Source operation
+24V
–
Sink operation
E
n
–
+24V
LED 0...15 Terminals
Description
Label
Address
Label
1 2
33 34
E
1
6
0
i