Saia-Burgess
Controls Ltd.
Hardware Manual for the PCD3 Series│Document 26/789; Version E 5│31.01.2005
Hardware
PCD3.H31x
5-88
5
*)
Balancing output voltage is carried out in the factory. The user is strongly advised
not to adjust the tuning potentiometer.
5V supply of 5V encoder for PCD2.H311
5V output:
5 V supply of encoder
Short circuit protection:
yes
Electrical isolation:
no
Output voltage:
5 V
Max. load current:
300 mA
Short circuit current:
400 mA (This current loads also the PCDs 5V bus)
Power supply
Internal current consumption:
(from +5 V bus)
max. 140 mA
typically 125 mA
Internal current consumption:
(from V+ bus)
0 mA
External current consumption:
typically 10 mA, max.15 mA
External supply
:
24 V
(19...32 V) smoothed, residual ripple max. 10%
Operational conditions
Ambient temperature:
operation 0...+55°C without forced ventilation
storage -20...+85°C
Interference immunity:
CE mark according to EN 50081-1 and EN 50082-2
Programming:
Based on PCD user program (PG5) and pre-pro-
grammed function blocks (FB). Motion X software
supports module initialization and commissioning (PID
values). Movements can be executed without a
user program. Values can be displayed both numerically
and graphically.
Terminal:
Pluggable 10-pole cage clamp terminal (4 405 4957 0)
or pluggable 10-pole screw terminal (4 405 4959 0) ,
both for wires up to 2.5 mm²