44 FP5/GP5 User’s Manual
n037 Multi-function input 2
(Terminal S3 Sel)
Set items are same as n036.
(When n036=”FWD/REV Cmd (3W), “In Use By
Other” is displayed, and setting is prohibited)
Ext
Fault
(NO)
78
n038 Multi-function input 3
(Terminal S4 Sel)
Set items are same as n036. Fault
Reset
78
n039 Multi-function input 4
(Terminal S5 Sel)
Set items are same as n036.
(When n040=”Up/Down Control”, “In Use By Other
is displayed, and setting is prohibited)
Multi-
Step
Spd 1
78
n040 Multi-function input 5
(Terminal S6 Sel)
Set items are same as n036.
LED
Setting
LCD Setting
Description
29 Up / Down control Up / Down command (Terminal
S5=Up command, and terminal
S6=Down command).
Multi-
Step
Spd 2
78
n041 Multi-function output
selection 1
(Terminal MA Sel)
LED
Setting
LCD Setting
Description
0 Fault Fault
1 During Running During running
2 At Speed Frequency agree
3 At Desired Speed Desired frequency agree
4 Freq Detection 1 Frequency detection 1
5 Freq detection 2 Frequency detection 2
6 OverTrq Det (NO) Over/Undertorque detection (nor-
mally open)
7 OverTrq Det (NC) Over/Undertorque detection (nor-
mally closed)
8 Baseblocked During baseblock
9 Operation Mode Local mode
10 Ready Inverter operation ready
11 Timer Output Timer function
12 Auto-Restarting During auto restart
13 OL Pre-Alarm OL pre-alarm (80% OL1 or OL2)
14 Freq Ref Loss Frequency reference loss
15 Set By COM Cntl Closed by serial communication
16 PID Fdbk Loss PID feedback loss
17 OH1 Alarm OH1 Alarm (set if n035 set to "3")
Fault 83
n042 Multi-function output
selection 2
(Terminal M1 Sel)
Set items are as same as n041 During
Running
83
n043 Master analog input selec-
tion - FV or FI terminal
(Analog Input Sel)
LED LCD
Setting Setting
FV
FI
Remarks
0 FV=MSTR FI=AUX Master Aux. Enable
1 FV=AUX FI=MSTR Aux. Master Enable
2 FV=RST FI=MSTR Fault reset Master Disable
Enable: FV/FI switchover function is enabled.
Disable: FV/FI switchover function is disabled.
Note: When PID is enabled (n084
≠
0),
FV terminal = PID reference, and
FI terminal = PID feedback.
FV=MSTR
FI=AUX
82
n044 Aux. analog input
selection
(Terminal FI Sel)
LED
Setting
LCD Setting
Description
0 0-10VDC 0~10V input (Jumper J1 must be cut)
1 4-20mA 4~20mA input
4-20mA 82
n045 Frequency reference
retention
(MOP Ref Memory)
LED
Setting
LCD Setting
Description
0 Memorize Fref Retained in frequency reference 1 (n024)
1 Not Memorized Not retained after power-down
Memorize
Fref
82
n046 Operation method for
frequency reference
loss detection
(Ref Loss Detect)
LED
Setting
LCD Setting
Description
0 Not detected No detection
1 Run @ n047 Fref Continue to run at n047 setting
Not
Detected
82
No. Function Name
(LCD Operator Display)
Description Factory
Default
User
Setting
Ref.
Page
Chapter 3 - Programming Features
FP5/GP5 Parameters