50 FP5/GP5User’s Manual
3.3 FP5/GP5 OPERATION
Accel/Decel Time Adjustment
When any of the multi-function input terminal selections (n036, n037, n038,
n039 or n040) is set to “Acc/Dec Switch”, accel/decel times can be selected
by opening or closing the appropriate terminal (S2, S3, S4, S5 or S6).
At OPEN: n018 (accel time 1), n019 (decel time 1)
At CLOSED: n020 (accel time 2), n021 (decel time 2)
* Setting unit is 1s for 1,000s and above.
· Acceleration time
Sets the time necessary for the output frequency to move from 0Hz to
maximum output frequency (n011).
· Deceleration time
Set the time necessary for the output frequency to move from maximum
output frequency (n011) to 0Hz.
Parameter No. Name Unit Setting Range Factory Default
n018 Acceleration time 1 0.1s * 0.0 to 3600s 10.0s
n019 Deceleration time 1 0.1s * 0.0 to 3600s 10.0s
n020 Acceleration time 2 0.1s * 0.0 to 3600s 10.0s
n021 Deceleration time 2 0.1s * 0.0 to 3600s 10.0s
Output
Frequency
Accel Time 1
(n018)
Decel Time 1 (n019)
Accel Time 2 (n020)
Decel Time 2* (n021)
Decel Time 1* (n019)
Time
FWD (REV) Run Command
ON OFF ON
ON
Accel/Decel Time Selection
(Terminals S2 to S6)
* When “deceleration to stop” is selected (n004 = “Ramp to STOP”)
Figure 18 Timing Diagram of Accel/Decel Time Adjustment