FP5/GP5 User’s Manual 71
Chapter 3 - Programming Features
FP5/GP5 Operation
· Coast to Stop with Timer 1 (n004 = “Coast w/Timer 1”)
Upon removal of the run command, the inverter output is immediately
removed, allowing the motor to coast. If the run command is re-applied
before the minimum baseblock time (n057) elapses, the run command is
not accepted.The run command must be cycled to be acknowledged. An
initial run command will be accepted if applied after the minimum base-
block time elapses.
· Coast to Stop with Timer 2 (n004 = “Coast w/Timer 2”)
Operation is disabled during the minimum baseblock time (n057) after a
stop command is given. A run command will be accepted, but operation
does not start until the minimum baseblock time runs out. The inverter
does not operate during the baseblock time, as shown in Figure 42.
Output Frequency
Coasting
Decel Time 1
(n019)
Accel Time 1
(n018)
Time
ON
ON
ON
FWD (REV)
Run Command
Run Command Disabled
Figure 41 Example of Stopping Method - Coast to Stop w/ Timer 1
Minimum baseblock time (n057)
Output Frequency
Coasting
Decel Time 1
(n019)
Accel Time 1
(n018)
Time
ON
ON
FWD (REV)
Run Command
Figure 42 Example of Stopping Method - Coast to Stop w/ Timer 2
Minimum baseblock time (n057)