Spiral
®
SST and STT Prewire Installation Manual
Spiral
®
SST and STT Prewire Installation Manual
■
1072124-0
■
Rev 03
■
01/22
30
Next: set limits
Do This
Result
1
Scrolling message:
Hold
Reset
button
if
position
OK
2
Scrolling message:
Hold
Reset
button
if
position
OK
Interrupt the set limits sequence
and run the tests
in
What to test after
powering up the door
on the next page.
3
Resume
the sequence and set the open position.
The top of the end brackets should align with the
bottom of the radial guide track.
Do This
Result
4
Scrolling message:
Press
Close
button
to
begin
5
6
▪
The door opens and closes automatically
up to 12 times
.
▪
The controller automatically sets the close limit
position while the door calibrates.
▪
When calibration is complete, the door switches
to Run mode.
The door may not open or close
completely
during automatic
calibration. This is normal.
When calibration is complete, the
door will open and close correctly.
▪
You can manually adjust the close limit after
calibration is complete by changing parameter
P:275.
See page 34.
_0 Press Reset
! Syncron.
!
until the “Syncron.” screen displays
_0 Hold Reset
!
To Open Pos.
RY-FT-000091
1x
to start sequence
_0 Hold Reset
!
To Open Pos.
RY-FT-000092
until open height is correct
_0
Open Limit Set
_0
LGx
Qual.
Check
_0 Press Close
! Syncron.
!
until “Open Limit Set” screen displays
when quality check is complete,
you see these screens:
-1330_Auto
Close
!
Search
Edge
Press
Open
butto
!Auto
Calibrate!
the door panel stops when
it reaches the bottom of the
light curtain, then you see:
1x
to start. The door panel closes.
I515
Limit
Corr.
Door
Is
Opening
Object
232
Acl1 = 4Sec
RY-UI-000050
I515
Limit
Corr.
Door
Is
Closing
RY-UI-000050
Object
232
Acl1 = 4Sec
[xxx]
Cycles
Spiral
1x
to start auto-calibration