Installation, operating and maintenance manual SKIT/S-DEB
3rd print version
page 63
11 – Maintenance
RWO GmbH
●
Marine Water Technology
●
Bremen
●
Germany
Issue 2014-04-10
Check the function of the heater (pos. 10), if
necessary, replace it.
11.4
Mounting the coalescer non-return flap
WARNING
Maintenance and repair work must only be done by
qualified and suitable personnel.
In particular observe the safety instructions in
à
chapter 2, the pertinent accident prevention
regulations and
the proper use of tools and lifting devices.
Note
The following spare parts and tools should be at
hand:
Coalescer key
à
chapter 13.10, table 26
Lid seals, pos. 31,
à
chapter 13, tables 18 -25.
Coalescer stuffing, pos. 34,
à
chapter 13, tables 18 -
25
Pliers for external circlip
Lifting equipment for oil separators with a power of
2.5 m³/h or more
Coalescer element – delivery condition up to SKIT/S-DEB
2.5 m³/h. As of SKIT/S-DEB, the non-return flap is
mounted outside of the coalescer container.
Fig. 12 Delivery condition
Remove the protective cap from the thread
Fig. 13 Cap
Mount the non-return flap
Note
The arrow must point towards the perforated plate.