SmartAlarm Instruction Manual Rev 2
Page 90 of 115
Please Note:-
The drop down menu within the configuration software allows the user to
select ISA Sequence A-4-5-6 to obtain Status Only indication.
If the audible alarm sounds on a channel that has been set to Status only
please check that the channel is not part of a
“Group” which has been
assigned to operate as an
“Audible” under the group operations tab.
In the example below Group 8 is being used as an audible group.
Group Tab
This screen shot indicates that a channel has been set to Group 8.
Group Operations Tab
This screen shot indicates that Group
“Type” for Group 8 has been set to
operate as
“Audible”.
To prevent the audible sounding the user should select the associated alarm
LED on the software faceplate and uncheck the tick box associated with any
Group being used as an Audible in the example above this would be Group 8.