SmartAlarm Instruction Manual Rev 2
Page 59 of 115
Inhibit Function
As an alternative any of the five pushbutton inputs can be set for use with an
external inhibit switch. The inhibit switch should be connected bVB
and the associated pushbutton input. When the switch is in the closed position
all alarms within the inhibit group will be prevented from operating until the
inhibit switch is returned to normal
It is possible to assign any channel with the Annunciator to be included in
inhibit group-1 to inhibit group-8 as required
To link a channel to an inhibit group first select the associated LED within the
software face
plate to access the “channel”-tab.
Under the
“Manual Inhibit” field assign the channel to an inhibit group as
required
and select “Confirm” followed by “Tools” – “Send Settings” to
download the settings to the Annunciator.
Assigning Channel to Inhibit Groups
In the above example channel 3 has been set to Inhibit Group 1