SmartAlarm Instruction Manual Rev 2
Page 30 of 115
Once the supply has been connected the signal supply voltage is
internally distributed to the signal common teVFC for
distribution to the field contacts. An internal 160mA glass quick blow
fuse, 5mm x 20mm, located on the Common Services Card is used to
protect the output from field wiring errors.
Signal Supply Fuse Location and FCV Link Details
A 160mA quick blow glass fuse 5 x 20mm is located on the Common
Services Card to protect the signal supply voltage.
VFC, (Voltage Field Contacts), Links LK1 and LK2 must be in the
external position.
F2
INT
EXT
LK1
VFC
VFC
LK2
EXT
INT
JUMPER
POSITIONS FOR
EXTERNAL
SIGNAL SUPPLY
160mA
Quick Blow
5 x 20mm
SIGNAL SUPPLY FUSE DETAILS
AND FCV JUMPER SETTINGS