SmartAlarm Instruction Manual Rev 2
Page 76 of 115
Input
The following options are available under the “Input” tab
Contact Type
A dropdown menu allows the user to assign the non-alarm contact state for
each channel. The default setting is Normally Open (Closed to alarm) with an
optional setting to Normally Closed (Open to alarm). If serial inputs are
required please select the tick-
box to the left of “Remote”
Delay Timers
Each channel is equipped with timers allowing the user to delay the activation
and/or the return to normal time period.
Abnormal Delay (mS)
This option prevents the alarm occurring before a pre-set time period has
elapsed. If an alarm occurs the timer will automatically start and the alarm will
occur as soon as the delay period has passed.
Normal Delay (mS)
This option prevents the alarm returning to normal until the pre-set delay
period has elapsed.
The default setting for the activation and deactivation is 10mS but can be
selected between 1 and 65,000mS as required.