SmartAlarm Instruction Manual Rev 2
Page 18 of 115
Diagnostic / Program mode - Dynamic Contact Status
The internal pushbuttons can be used to view the dynamic state of all signal
inputs by pressing and holding the internal
Test
pushbutton for 10 seconds.
Test
Mute
Ack
Reset
PSU
WD
1
2
RTK SmartAlarm
Isolate Live Voltage before access
!
1
2
3
4
5
8
PRESS AND HOLD FOR 10 SEC'S
7
6
LED-1, located above the test pushbutton, slow flashes to indicate the
Annunciator is in monitor mode.
Whilst in this mode the individual channel LED provides the dynamic status of
the associated field contacts.
If the LED is ON the field contact is CLOSED.
If the LED is OFF the field contact is OPEN.
This is a quick method of verifying the dynamic state of the field contact and is
typically used during commissioning or fault finding.
The contact monitoring function times out after 1 minute and the unit
automatically returns to the normal run mode and LED-1 reverts to steady
ON.