Smart Positioner
YT-3100
Product Manual
Ver. 1.19
35
Level 1
Level 2
Range
Initial factory setting
Input Configuration
[IN CFG]
Characterization [CHAR]
Linear, Quick Open,
Equal Percent, User Set
5point, User Set 21point
[LIN, QO, EQ, U5, U21]
LIN
User Set Characterization 5p
[USER 5P]
0 %, 25 %, 50 %, 75 %,
100 %
User Set Characterization 21p
[USER 21P]
0 %, 5 %, 10 %, … 95 %,
100 %
Tight Shut Open [TSHUT OP]
0.1 ~ 100 [%]
100.0 %
Tight Shut Close [TSHUT CL]
0.1 ~ 100 [%]
0.3 %
Output Configuration
[OUT CFG]
Position Transmitter Direction
[PTM]
[NORM, REVS]
NORM
Position Transmitter Zero
[PTM ZERO]
0 ~ 100.00 [%]
Position Transmitter End
[PTM ENd]
0 ~ 100.00 [%]
Back Calculation [bAKCAL]
[oFF, on]
oFF
Device Configuration
[dEV CFG]
Action Change [ACT]
[dIR, REVS]
REVS
Linear Interpolation [ITP]
[oFF, on]
on with Linear
oFF with Rotary
Write Protect [W]
[UNLOCK, LOCK]
UNLOCK
View Mode [VI]
[NORM, REVS]
NORM
Factory Reset [dEFAULT]
Self-Test [SELFTEST]
Diagnosis [dIAGNO]
Device Status [dS]
GOOd, Refer to 9.15 Status
and Alarm Code.
GOOd
Reset Alarm Status [RST ALRM]
View Event Log [EVT LOG]
RECORD 0 - 19
1
Information [INFO]
Model Name [YT3100*]
Firmware Version [SOFT VER]
Download Date
*.*.**
YYYYMMDD
Program current version
Program input date
Run Time [RT]
*.**
RT *d
Upward Stroke Time [FULL OP]
**.**
Downward Stroke Time
[FULL CL]
**.**
Position Sensor Type [PSNT]
PTN, NCS
Absolute Position in Angle
[AbS ANGL]
***.* °
Содержание YT-3100
Страница 1: ...SMART POSITIONER PRODUCT MANUAL YT 3100 VERSION 1 19 Rotork YTC Limited...
Страница 9: ...Smart Positioner YT 3100 Product Manual Ver 1 19 9 Fig L 3 Intrinsic safety type CCC...
Страница 14: ...Smart Positioner YT 3100 Product Manual Ver 1 19 14 2 8 Product Dimension Fig 2 2 YT 3100L Fig 2 3 YT 3100R...
Страница 67: ...Smart Positioner YT 3100 Product Manual Ver 1 19 67 10 Main Software Map...