3.3
Linear positioner Installation
Linear positioner should be installed on linear motion valves such as globe or gate type which uses
spring return type diaphragm or piston actuators.
Fig. 3-2: installation example
Before proceeding with the installation, ensure following components are available.
➢
Positioner
➢
Feedback lever and lever spring
➢
M6 nut and spring washer (fastening feedback lever to a main shaft)
➢
Bracket, bolts and washers for positioner or sensor – not supplied with the positioner
➢
Connection bar – not supplied with the positioner
3.3.1
Safety
Proper bracket must be made in order to adapt the positioner on the actuator yoke.
Please consider following important points when a bracket is being designed.
➢
Positioner’s feedback lever must be vertical to the valve stem at 50 % of the valve stroke.
➢
The connection bar of the actuator clamp for the feedback lever should be installed in such a way
that the valve stroke length coincides with the corresponding figure in “mm” marked on the
feedback lever. Improper setting may cause poor linearity