4 Installation

Installation manual

16

R2CND0 R2TND012~024A4AA

Wall-mounted condensing boiler

3P469346-4E – 2017.07

Symbols:

Item

Description

Option

Wiring depending on model

Switch box

PCB

X4M

Main terminal

Earth wiring

15

Wire number 15

Field supply

1

Several wiring possibilities

Legend:

Part

Connector

Description

PCB1

Main PCB

PCB2

X3

Status indicator PCB

PCB3

X9

LAN (var iCAN) adapter

P1

X2-X11

Boiler pump

F1

X1-X11

Fan

GV1

X11

Gas valve

IT1

X1

Ignition transformer

3WV1

X13

Central heating / domestic hot
water diverter valve stepper
motor

WPS1

X4

Water pressure sensor

DHW FS1

X4

Domestic hot water flow sensor
(for models R2CND024A4AA)

IE1

X5

Ionisation input

K1

X2M

Solar stop contact

K2

X2M

On/OFF room thermostat

HE1

X11

Overheat thermostat

NTC1

X1M

Outdoor temperature sensor

NTC2

X4

Flow temperature sensor

NTC3

X4

Return temperature sensor

NTC4

X4

Flue temperature sensor

NTC5

X4

Domestic hot water temperature
sensor

(for models R2CND024A4AA)

NTC5

X1M

Domestic hot water storage tank
sensor

(for models R2TND012A4AA,
R2TND018A4AA and
R2TND024A4AA)

NTC6

X1M

Solar domestic hot water
temperature sensor

Ext1

X8

BCC (Boiler Chip Card)

Ext2

X10

Personal computer production
interface

Ext3

X1M

Opentherm room thermostat

Ext4

X2M

External power output
(230 V AC)

Ext5

X2M

Reserved, not in use

X1M

X4-X11-X12

Low voltage terminal strip

X2M

X1-X2

High voltage terminal strip

4.8.7

Guidelines when connecting the
condensate piping

DANGER

In order to prevent escape of flue gases and so poisoning,
the  condensate  trap  must  be  mounted  to  its  place  before
commissioning.

Condensate  trap  must  be  connected  to  a  drain  via  an  open
connection.

Precautions that should be taken about condensate piping are:

▪ Horizontal pipe runs must fall a minimum of 45 mm/metre.

▪ External  piping  should  be  kept  as  short  as  possible  or  thermally

insulated to prevent freezing, depending on the installation winter
climate condition.

▪ Make  sure  that  the  condensate  disposal  system,  the  piping,  and

the fittings are made of acid resistant material like plastics.

WARNING

The  condensate  trap  outlet  shall  not  be  modified  or
blocked.

CAUTION

The  condensate  discharge  piping  diameter  must  be  large
enough so as not to restrain the condensate water flow.

WARNING

If  the  discharge  pipe  is  located  outdoors,  take  measures
against frost.

4.8.8

Guidelines for condensate piping
termination

Condensate  piping  can  be  connected  to  a  termination  in  different
ways shown below:

Terminating into an internal soil and vent stack

b

a

≥450 mm

a

Air breaker

b

Internal soil and vent stack

Terminating into an external waste system

a

Содержание R2TND012A4AA

Страница 1: ...Installation manual Wall mounted condensing boiler English Installation manual Wall mounted condensing boiler R2CND024A4AA R2TND012A4AA R2TND018A4AA R2TND024A4AA...

Страница 2: ...is t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra n...

Страница 3: ...propriately disposed of in accordance with local and national regulations The components are easy to separate and the plastics are marked This allows the various components to be sorted for appropriat...

Страница 4: ...ommissioning repair configuration and service must be performed by qualified competent persons in accordance with local standards and regulations Incorrect installation of this unit may harm the user...

Страница 5: ...es It is controlled by the flow temperature sensor which is located at the outlet of the main heat exchanger This protection activates the boiler pump when the water temperature drops below 13 C and i...

Страница 6: ...rode p High limit thermostat q Fan r Return temperature sensor s Silencer t Automatic air vent pump u Water pressure sensor v By pass w Boiler pump x Domestic hot water flow sensor y Domestic hot wate...

Страница 7: ...max m h 0 12 0 46 0 12 0 69 0 12 0 96 0 12 0 96 Combustion products mass flow rate min max G20 g s 1 32 5 12 1 32 7 78 1 32 10 75 1 32 10 75 Combustion products mass flow rate min max G31 g s 1 23 4 7...

Страница 8: ...ters 50 C return temperature at heater inlet 4 Installation 4 1 To open the unit WARNING Only qualified competent persons are allowed to open the unit Certain actions explained in this document such a...

Страница 9: ...the current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake air must not include chemicals that may cause corrosion toxic gas format...

Страница 10: ...ght and related system charge pressure are given below h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0 bar 9 m 1 1 bar 10 m 1 2 bar 11 m 1 3 bar 12 m 1 4 bar 13 m 1 5 bar h h System water height m p System charge...

Страница 11: ...done to avoid discomfort of the user 4 7 Residual pump lift graph The residual pump lift graph shows the amount of pump lift mbar that remains for the central heating circuit 0 0 100 200 300 400 500 6...

Страница 12: ...ge while the gas line to the boiler is open see 5 3 To check for gas leakage on page 24 In case gas piping is adjacent to the wall and is to be connected to the gas pipe connection of the boiler with...

Страница 13: ...ny damage that may occur this way WARNING Use a dedicated power circuit Never use a power supply cable shared by another unit The unit runs on 230 V AC 50 Hz power A power cable is delivered with the...

Страница 14: ...nds that are sent with the unit must be assembled to the bottom sheet of the boiler in case connection of these options Below you can see the cable glands placement PG 9 PG 9 PG 7 PG 7 Holes on the bo...

Страница 15: ...012 024A4AA Wall mounted condensing boiler 3P469346 4E 2017 07 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Model R2CND024A4A...

Страница 16: ...ace Ext3 X1M Opentherm room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1M X4 X11 X12 Low voltage terminal strip X2M X1 X2 High voltage terminal strip 4 8 7 Guidel...

Страница 17: ...that products of combustion discharging from the terminal cannot re enter the building or other buildings through ventilators windows doors other sources of natural air infiltration or forced ventila...

Страница 18: ...it Optional c 45 elbow 60 100 d Extension 60 100 mm e Flat roof outlet kit f 90 elbow 60 100 g 45 elbow 60 100 h 30 elbow 60 100 i Extension 60 100 L 500 1000 mm Allowable flue length for C33x R2TND R...

Страница 19: ...nd lengths of the flue system For R2TND Nominal combustion products temperature 77 C Combustion products mass flow rate 10 75 g s Overheat combustion products temperature 90 C Minimum combustion produ...

Страница 20: ...use flue outlet duct length must be shortened with the same length Type C83x twin pipes flue system The boiler draws combustion air from outside via a separate supply pipe routed through the external...

Страница 21: ...h 140 19 6 69 2 DN 80 Flex square and rough 130 17 0 60 0 DN 80 Flex square and rough 120 12 2 43 0 DN 80 Star square and rough 140 47 5 167 8 DN 80 Star square and rough 120 33 3 117 9 Allowable flue...

Страница 22: ...e 60 100 with measurement point EKFGP4667 90 elbow 60 100 with measurement point DRMEEA60100BA 90 elbow 60 100 EKFGP4660 90 elbow 80 125 EKFGP4810 45 elbow 60 100 EKFGP4661 45 elbow 80 125 EKFGP4811 3...

Страница 23: ...om the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting 10 If after the venting the pressure decreases below 0 8 bar refill with water until t...

Страница 24: ...Back button INFORMATION Only qualified persons have access to servicing parameters The passwords needed to access service parameters are written in servicing instructions 5 Commissioning WARNING Only...

Страница 25: ...buttons together five seconds Sweeper mode will be deactivated and boiler will return to normal operation mode Sweeper mode also finishes automatically after 15 minutes 5 4 2 To commission the centra...

Страница 26: ......

Страница 27: ......

Страница 28: ...usland Our partners abroad Unsere Partner im Ausland Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani http...

Отзывы: