4 Installation

Installation manual

13

R2CND0 R2TND012~024A4AA
Wall-mounted condensing boiler
3P469346-4E – 2017.07

▪ The maximum pressure in the domestic hot water circuit is 10 bar.

Inspect  the  piping  taking  this  in  to  consideration.  If  the  water
pressure  of  the  main  water  supply  is  excessive,  use  an
appropriate  pressure  reducer.  Installation  must  comply  with
EN 15502-2-2.

▪ As  the  condensing  boilers  generate  condensate,  the  condensate

trap  outlet  should  be  connected  to  an  open  drain.  Piping  and
elements of the drain line must be made of acid-resistant material
like plastics. Metals like steel or copper are not allowed.

▪ The  system  must  be  air-free  to  protect  the  boiler.  There  are  two

automatic air vents on the boiler, one at heat exchanger, the other
on  the  pump.  Ensure  air  is  discharged  completely  at  each  water
filling. Bleed the radiators if necessary.

▪ If  the  boiler  will  be  connected  to  an  old  central  heating/domestic

hot water installation, then first visually inspect the old installation.
The  installation  must  be  in  compliance  with  the  capacity  of  the
boiler  and  must  not  prevent  the  efficient  running  of  it.  Dirt  in  old
system and piping must be flushed, and filters must be inspected.

▪ If old piping material does not have oxygen barrier, then it must be

separated from the boiler circuit via a plate heat exchanger and a
second pump has to be installed for necessary circulation.

▪ If  the  pressure  reading  on  the  boiler  user  interface  is  dropping

repeatedly,  most  probably  there  is  a  leakage  in  the  installation.
Inspect the installation to repair.

▪ In case of solar preheating of the domestic hot water from a solar

tank,  install  the  thermostatic  mixing  valve  at  the  domestic  hot
water outlet and inlet.

4.8.4

Guidelines when connecting the electrical
wiring

DANGER

Before  working  on  the  electrical  circuit  always  isolate  the
unit from the power mains.

WARNING

Only  qualified  persons  are  allowed  to  make  electrical
connections on the unit. Failure to observe this warning will
void the warranty. The manufacturer is not responsible for
any damage that may occur this way.

WARNING

Use  a  dedicated  power  circuit.  Never  use  a  power  supply
cable shared by another unit.

The unit runs on 230 V AC 50 Hz power. A power cable is delivered
with the package. The power cable must be connected to the power
supply  by  an  electrician  and  in  accordance  with  the  applicable
legislation.

a

b

3×0.75 TTR / 230 V

H05RN

1~ 230 V

50 Hz

Cat. III

a

Safety breaker (2 A)

b

Earth leakage safety breaker

Cat. III

Overvoltage category III

▪ Electrical  work  should  be  carried  out  in  accordance  with  the

installation manual and the national electrical wiring rules or code
of practice.

▪ Insufficient  capacity  or  incomplete  electrical  work  may  cause

electrical shock or fire.

▪ A main switch or other means for disconnection, having a contact

separation  in  all  poles  providing  full  disconnection  under
overvoltage category III, shall be installed in the fixed wiring.

▪ Be sure to establish an earth. Do not earth the unit to a utility pipe,

lightning  arrester,  or  telephone  earth. 

Incomplete  earth  may

cause electrical shock and fire.

▪ While  the  electrical  connections  are  being  done,  energy  should

not  be  on  the  main  power  supply  cable  and  the  main  switch
should be closed.

▪ During  the  electrical  connections,  make  sure  that  the  cables  are

well-fixed and are connected firmly and tightly.

▪ Power  supply  cable  must  be  equivalent  to 

H05RN-F  (2451EC57)

as minimum requirement.

Observe the point mentioned below when wiring to the power supply
terminal board.

b

a

L

N

a<b

WARNING

Do  not  interchange  the  supply  conductors  L  and  the
neutral conductor N.

DANGER

Do not use gas and water pipes for earthing purposes and
ensure  that  they  have  not  been  used  for  this  purpose
before. Failure to observe this relieves the manufacturer of
any responsibility.

4.8.5

Guidelines when connecting options to
the boiler

Optional  equipment  is  connected  to  the  connectors,  which  are
located on the outside of the switch box. Do not open the switch box
to connect optional equipment.

Temperature control units

Connector

Connection

Solar NTC sensor

X1M

1-2

Opentherm room thermostat

X1M

3-4

Outdoor sensor

X1M

5-6

Domestic hot water storage tank
sensor

X1M

7-8

External power output (230 V AC)

X2M

3-4

On-Off room thermostat

X2M

5-6

Solar stop contact

X2M

7-8

X1M

Содержание R2TND012A4AA

Страница 1: ...Installation manual Wall mounted condensing boiler English Installation manual Wall mounted condensing boiler R2CND024A4AA R2TND012A4AA R2TND018A4AA R2TND024A4AA...

Страница 2: ...is t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra n...

Страница 3: ...propriately disposed of in accordance with local and national regulations The components are easy to separate and the plastics are marked This allows the various components to be sorted for appropriat...

Страница 4: ...ommissioning repair configuration and service must be performed by qualified competent persons in accordance with local standards and regulations Incorrect installation of this unit may harm the user...

Страница 5: ...es It is controlled by the flow temperature sensor which is located at the outlet of the main heat exchanger This protection activates the boiler pump when the water temperature drops below 13 C and i...

Страница 6: ...rode p High limit thermostat q Fan r Return temperature sensor s Silencer t Automatic air vent pump u Water pressure sensor v By pass w Boiler pump x Domestic hot water flow sensor y Domestic hot wate...

Страница 7: ...max m h 0 12 0 46 0 12 0 69 0 12 0 96 0 12 0 96 Combustion products mass flow rate min max G20 g s 1 32 5 12 1 32 7 78 1 32 10 75 1 32 10 75 Combustion products mass flow rate min max G31 g s 1 23 4 7...

Страница 8: ...ters 50 C return temperature at heater inlet 4 Installation 4 1 To open the unit WARNING Only qualified competent persons are allowed to open the unit Certain actions explained in this document such a...

Страница 9: ...the current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake air must not include chemicals that may cause corrosion toxic gas format...

Страница 10: ...ght and related system charge pressure are given below h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0 bar 9 m 1 1 bar 10 m 1 2 bar 11 m 1 3 bar 12 m 1 4 bar 13 m 1 5 bar h h System water height m p System charge...

Страница 11: ...done to avoid discomfort of the user 4 7 Residual pump lift graph The residual pump lift graph shows the amount of pump lift mbar that remains for the central heating circuit 0 0 100 200 300 400 500 6...

Страница 12: ...ge while the gas line to the boiler is open see 5 3 To check for gas leakage on page 24 In case gas piping is adjacent to the wall and is to be connected to the gas pipe connection of the boiler with...

Страница 13: ...ny damage that may occur this way WARNING Use a dedicated power circuit Never use a power supply cable shared by another unit The unit runs on 230 V AC 50 Hz power A power cable is delivered with the...

Страница 14: ...nds that are sent with the unit must be assembled to the bottom sheet of the boiler in case connection of these options Below you can see the cable glands placement PG 9 PG 9 PG 7 PG 7 Holes on the bo...

Страница 15: ...012 024A4AA Wall mounted condensing boiler 3P469346 4E 2017 07 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Model R2CND024A4A...

Страница 16: ...ace Ext3 X1M Opentherm room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1M X4 X11 X12 Low voltage terminal strip X2M X1 X2 High voltage terminal strip 4 8 7 Guidel...

Страница 17: ...that products of combustion discharging from the terminal cannot re enter the building or other buildings through ventilators windows doors other sources of natural air infiltration or forced ventila...

Страница 18: ...it Optional c 45 elbow 60 100 d Extension 60 100 mm e Flat roof outlet kit f 90 elbow 60 100 g 45 elbow 60 100 h 30 elbow 60 100 i Extension 60 100 L 500 1000 mm Allowable flue length for C33x R2TND R...

Страница 19: ...nd lengths of the flue system For R2TND Nominal combustion products temperature 77 C Combustion products mass flow rate 10 75 g s Overheat combustion products temperature 90 C Minimum combustion produ...

Страница 20: ...use flue outlet duct length must be shortened with the same length Type C83x twin pipes flue system The boiler draws combustion air from outside via a separate supply pipe routed through the external...

Страница 21: ...h 140 19 6 69 2 DN 80 Flex square and rough 130 17 0 60 0 DN 80 Flex square and rough 120 12 2 43 0 DN 80 Star square and rough 140 47 5 167 8 DN 80 Star square and rough 120 33 3 117 9 Allowable flue...

Страница 22: ...e 60 100 with measurement point EKFGP4667 90 elbow 60 100 with measurement point DRMEEA60100BA 90 elbow 60 100 EKFGP4660 90 elbow 80 125 EKFGP4810 45 elbow 60 100 EKFGP4661 45 elbow 80 125 EKFGP4811 3...

Страница 23: ...om the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting 10 If after the venting the pressure decreases below 0 8 bar refill with water until t...

Страница 24: ...Back button INFORMATION Only qualified persons have access to servicing parameters The passwords needed to access service parameters are written in servicing instructions 5 Commissioning WARNING Only...

Страница 25: ...buttons together five seconds Sweeper mode will be deactivated and boiler will return to normal operation mode Sweeper mode also finishes automatically after 15 minutes 5 4 2 To commission the centra...

Страница 26: ......

Страница 27: ......

Страница 28: ...usland Our partners abroad Unsere Partner im Ausland Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani http...

Отзывы: