4 Installation

Installation manual

10

R2CND0 R2TND012~024A4AA

Wall-mounted condensing boiler

3P469346-4E – 2017.07

4.4

To mount the unit

1

The  mounting  template  shows  the  position  for  the  horizontal
flue. If there is no hole in the wall for the flue piping, drill one. If
there  is  already  a  hole  in  the  wall  for  the  flue  piping,  you  can
use this hole as a starting point to determine the position of the
mounting  bracket,  according  to  the  template.  Flue  duct  must
incline  3°  away  from  the  unit,  to  allow  the  condensate  to  drain
back to the boiler.

>3°

200

127

200

DN100

>3°

2

Drill  holes  for  the  mounting  bracket  (Ø10  mm).  Fasten  the
mounting bracket to the wall according to mounting template.

d=10 mm

3

Hang  the  unit  on  the  bracket.  Make  sure  the  unit  is  latched  to
the bracket.

4.5

Central heating system
requirements

Expansion vessel sizing

The boiler is equipped with an 8 litre expansion vessel that has initial
charge pressure of 1 bar.

Sufficiency  of  the  incorporated  expansion  vessel  for  the  central
heating  circuit  that  the  boiler  is  to  be  connected  to  depends  on
system  charge  pressure  and  water  temperature  circulating  in  the
circuit.

Determination  of  system  water  height  and  related  system  charge
pressure are given below:

h

p

≤6 m

0.8 bar

7 m

0.9 bar

8 m

1.0 bar

9 m

1.1 bar

10 m 1.2 bar

11 m

1.3 bar

12 m 1.4 bar

13 m 1.5 bar

h

h

System water height (m)

p

System charge pressure (bar)

According  to  the  graph  below,  there  is  no  need  to  install  an
additional  expansion  vessel  for  the  systems  with  a  water  volume  in
the  area  below  the  operating  temperature  curve.  If  water  volume  is
above  the  curve,  additional  vessel  must  be  installed,  preferably  on
the return to the boiler.

A (l)

B (bar)

0.8

0

50

100

150

200

250

300

350

50°C-30°C

50°C-40°C*

60°C-40°C

70°C-50°C
80°C-60°C

0.9

1.0

1.1

1.3

1.2

1.4

1.5

A

System water volume (l)

B

System charge pressure (bar)

*

50°C-40°C temperature regime is given for underfloor
heating systems

Water treatment

Inappropriate  central  heating  circuit  water  reduces  functionality  and
efficiency of the boiler over time. Appropriate water should have:

▪ pH degree between 6.5 and 8.5

▪ Hardness less than 15°fH and 8.4°dH

Appropriate additives can be used for water treatment.

If antifreeze is needed for the system, the chosen antifreeze should
not  interact  with  rubber,  commercial  plastic  and  metal  parts  of  the
boiler that are in contact with the central heating water.

For use of any additive in the central heating system, please refer to
the instructions of their manufacturers to ensure above functionality
and compatibility.

Содержание R2TND012A4AA

Страница 1: ...Installation manual Wall mounted condensing boiler English Installation manual Wall mounted condensing boiler R2CND024A4AA R2TND012A4AA R2TND018A4AA R2TND024A4AA...

Страница 2: ...is t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra n...

Страница 3: ...propriately disposed of in accordance with local and national regulations The components are easy to separate and the plastics are marked This allows the various components to be sorted for appropriat...

Страница 4: ...ommissioning repair configuration and service must be performed by qualified competent persons in accordance with local standards and regulations Incorrect installation of this unit may harm the user...

Страница 5: ...es It is controlled by the flow temperature sensor which is located at the outlet of the main heat exchanger This protection activates the boiler pump when the water temperature drops below 13 C and i...

Страница 6: ...rode p High limit thermostat q Fan r Return temperature sensor s Silencer t Automatic air vent pump u Water pressure sensor v By pass w Boiler pump x Domestic hot water flow sensor y Domestic hot wate...

Страница 7: ...max m h 0 12 0 46 0 12 0 69 0 12 0 96 0 12 0 96 Combustion products mass flow rate min max G20 g s 1 32 5 12 1 32 7 78 1 32 10 75 1 32 10 75 Combustion products mass flow rate min max G31 g s 1 23 4 7...

Страница 8: ...ters 50 C return temperature at heater inlet 4 Installation 4 1 To open the unit WARNING Only qualified competent persons are allowed to open the unit Certain actions explained in this document such a...

Страница 9: ...the current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake air must not include chemicals that may cause corrosion toxic gas format...

Страница 10: ...ght and related system charge pressure are given below h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0 bar 9 m 1 1 bar 10 m 1 2 bar 11 m 1 3 bar 12 m 1 4 bar 13 m 1 5 bar h h System water height m p System charge...

Страница 11: ...done to avoid discomfort of the user 4 7 Residual pump lift graph The residual pump lift graph shows the amount of pump lift mbar that remains for the central heating circuit 0 0 100 200 300 400 500 6...

Страница 12: ...ge while the gas line to the boiler is open see 5 3 To check for gas leakage on page 24 In case gas piping is adjacent to the wall and is to be connected to the gas pipe connection of the boiler with...

Страница 13: ...ny damage that may occur this way WARNING Use a dedicated power circuit Never use a power supply cable shared by another unit The unit runs on 230 V AC 50 Hz power A power cable is delivered with the...

Страница 14: ...nds that are sent with the unit must be assembled to the bottom sheet of the boiler in case connection of these options Below you can see the cable glands placement PG 9 PG 9 PG 7 PG 7 Holes on the bo...

Страница 15: ...012 024A4AA Wall mounted condensing boiler 3P469346 4E 2017 07 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Model R2CND024A4A...

Страница 16: ...ace Ext3 X1M Opentherm room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1M X4 X11 X12 Low voltage terminal strip X2M X1 X2 High voltage terminal strip 4 8 7 Guidel...

Страница 17: ...that products of combustion discharging from the terminal cannot re enter the building or other buildings through ventilators windows doors other sources of natural air infiltration or forced ventila...

Страница 18: ...it Optional c 45 elbow 60 100 d Extension 60 100 mm e Flat roof outlet kit f 90 elbow 60 100 g 45 elbow 60 100 h 30 elbow 60 100 i Extension 60 100 L 500 1000 mm Allowable flue length for C33x R2TND R...

Страница 19: ...nd lengths of the flue system For R2TND Nominal combustion products temperature 77 C Combustion products mass flow rate 10 75 g s Overheat combustion products temperature 90 C Minimum combustion produ...

Страница 20: ...use flue outlet duct length must be shortened with the same length Type C83x twin pipes flue system The boiler draws combustion air from outside via a separate supply pipe routed through the external...

Страница 21: ...h 140 19 6 69 2 DN 80 Flex square and rough 130 17 0 60 0 DN 80 Flex square and rough 120 12 2 43 0 DN 80 Star square and rough 140 47 5 167 8 DN 80 Star square and rough 120 33 3 117 9 Allowable flue...

Страница 22: ...e 60 100 with measurement point EKFGP4667 90 elbow 60 100 with measurement point DRMEEA60100BA 90 elbow 60 100 EKFGP4660 90 elbow 80 125 EKFGP4810 45 elbow 60 100 EKFGP4661 45 elbow 80 125 EKFGP4811 3...

Страница 23: ...om the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting 10 If after the venting the pressure decreases below 0 8 bar refill with water until t...

Страница 24: ...Back button INFORMATION Only qualified persons have access to servicing parameters The passwords needed to access service parameters are written in servicing instructions 5 Commissioning WARNING Only...

Страница 25: ...buttons together five seconds Sweeper mode will be deactivated and boiler will return to normal operation mode Sweeper mode also finishes automatically after 15 minutes 5 4 2 To commission the centra...

Страница 26: ......

Страница 27: ......

Страница 28: ...usland Our partners abroad Unsere Partner im Ausland Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani http...

Отзывы: