4 Installation

Installation manual

17

R2CND0 R2TND012~024A4AA
Wall-mounted condensing boiler
3P469346-4E – 2017.07

a

Open end direct into gully, below ground but above water
level

Terminating into an external purpose made soakaway

a

b

a

Open end direct into gully, below ground but above water
level

b

Sink, basin, bath or shower

NOTICE

Use  of  a  condensate  drain  pump  is  necessary  where
termination of condensate line is below a soakaway.

4.8.9

Guidelines when connecting the boiler to
the flue gas system

DANGER

Risk of poisoning due to flue gas escaping within enclosed
rooms that are inadequately ventilated.

CAUTION

Connected flue type must be identified on the identification
label.

Approved flue systems

Choose a flue type according to the installation site.

Approved flue types are written on the identification label.

Flue termination

The positions of the terminals in the roof or in the wall with respect to
openings  for  ventilation  must  be  in  accordance  with  national
regulations.

▪ The  boiler  must  be  installed  so  that  the  terminal  is  exposed  to

external air.

▪ Position of the terminal must allow the free passage of air across it

at all times.

▪ Pluming may occur at the flue terminal. Positions where this could

be a nuisance should be avoided.

▪ For  single  wall  flue  pipe,  the  minimum  distance  to  a  combustible

material must be 25 mm.
For  air  intake  pipe  and  concentric  systems,  the  distance  to  a
combustible material is 0 (zero) mm.

▪ It  is  essential  to  ensure  that  products  of  combustion  discharging

from  the  terminal  cannot  re-enter  the  building  or  other  buildings,
through  ventilators,  windows,  doors,  other  sources  of  natural  air
infiltration or forced ventilation.

▪ Minimum flue duct length must be 50 cm.

4.8.10

Applicable flue systems

In  this  part,  information  about  different  flue  systems  are  given.  The
mounting  instructions  for  correct  installation  of  the  flue  systems  are
included  in  the  packaging  of  the  flue  parts  as  well  as  flue  cutting
instructions where needed.

NOTICE

Optional  parts  shown  in  rectangular  area  are  used  where
needed.

Type C13x (concentric flue system)

The  boiler  draws  combustion  air  from  outside  via  a  concentric
coaxial  pipe  fitted  to  the  external  wall  and  expels  flue  gas  to  the
outside via the external wall.

a

b

c

d

e

L

f

a

Wall terminal kit 60/100

Optional:

b

90° elbow 60/100

c

45° elbow 60/100

d

30° elbow 60/100

e

Tee 60/100 with measurement point

f

Extension 60/100
L = 500-1000 mm

Allowable flue length for C13x

R2TND*

R2CND*

Concentric 60/100 mm

(a)

11.0 m

8.1 m

Concentric 80/125 mm

(a)

44.0 m

26.2 m

(a)

Including 1 90° elbow

Equivalent length of options

90° elbow 60/100 mm

1.5 m

45° elbow 60/100 mm

1.0 m

30° elbow 60/100 mm

1.0 m

90° elbow 80/125 mm

1.5 m

45° elbow 80/125 mm

1.0 m

30° elbow 80/125 mm

1.0 m

60/100  flue  length  can  be  increased  up  to  17.9  metres  (for

R2TND*

) / 14.1 metres (for 

R2CND*

 )by adjusting the parameter

C3 to 3. Refer to servicing instructions for this operation.

Subtract  equivalent  length  value  of  bends  from  the  allowable  flue
length value.

DANGER

Flue  duct  must  incline  3°  away  from  the  unit,  to  allow  the
condensate  to  drain  back  to  the  boiler  and  out  of  the
condensate drain.

Содержание R2TND012A4AA

Страница 1: ...Installation manual Wall mounted condensing boiler English Installation manual Wall mounted condensing boiler R2CND024A4AA R2TND012A4AA R2TND018A4AA R2TND024A4AA...

Страница 2: ...is t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra n...

Страница 3: ...propriately disposed of in accordance with local and national regulations The components are easy to separate and the plastics are marked This allows the various components to be sorted for appropriat...

Страница 4: ...ommissioning repair configuration and service must be performed by qualified competent persons in accordance with local standards and regulations Incorrect installation of this unit may harm the user...

Страница 5: ...es It is controlled by the flow temperature sensor which is located at the outlet of the main heat exchanger This protection activates the boiler pump when the water temperature drops below 13 C and i...

Страница 6: ...rode p High limit thermostat q Fan r Return temperature sensor s Silencer t Automatic air vent pump u Water pressure sensor v By pass w Boiler pump x Domestic hot water flow sensor y Domestic hot wate...

Страница 7: ...max m h 0 12 0 46 0 12 0 69 0 12 0 96 0 12 0 96 Combustion products mass flow rate min max G20 g s 1 32 5 12 1 32 7 78 1 32 10 75 1 32 10 75 Combustion products mass flow rate min max G31 g s 1 23 4 7...

Страница 8: ...ters 50 C return temperature at heater inlet 4 Installation 4 1 To open the unit WARNING Only qualified competent persons are allowed to open the unit Certain actions explained in this document such a...

Страница 9: ...the current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake air must not include chemicals that may cause corrosion toxic gas format...

Страница 10: ...ght and related system charge pressure are given below h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0 bar 9 m 1 1 bar 10 m 1 2 bar 11 m 1 3 bar 12 m 1 4 bar 13 m 1 5 bar h h System water height m p System charge...

Страница 11: ...done to avoid discomfort of the user 4 7 Residual pump lift graph The residual pump lift graph shows the amount of pump lift mbar that remains for the central heating circuit 0 0 100 200 300 400 500 6...

Страница 12: ...ge while the gas line to the boiler is open see 5 3 To check for gas leakage on page 24 In case gas piping is adjacent to the wall and is to be connected to the gas pipe connection of the boiler with...

Страница 13: ...ny damage that may occur this way WARNING Use a dedicated power circuit Never use a power supply cable shared by another unit The unit runs on 230 V AC 50 Hz power A power cable is delivered with the...

Страница 14: ...nds that are sent with the unit must be assembled to the bottom sheet of the boiler in case connection of these options Below you can see the cable glands placement PG 9 PG 9 PG 7 PG 7 Holes on the bo...

Страница 15: ...012 024A4AA Wall mounted condensing boiler 3P469346 4E 2017 07 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Model R2CND024A4A...

Страница 16: ...ace Ext3 X1M Opentherm room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1M X4 X11 X12 Low voltage terminal strip X2M X1 X2 High voltage terminal strip 4 8 7 Guidel...

Страница 17: ...that products of combustion discharging from the terminal cannot re enter the building or other buildings through ventilators windows doors other sources of natural air infiltration or forced ventila...

Страница 18: ...it Optional c 45 elbow 60 100 d Extension 60 100 mm e Flat roof outlet kit f 90 elbow 60 100 g 45 elbow 60 100 h 30 elbow 60 100 i Extension 60 100 L 500 1000 mm Allowable flue length for C33x R2TND R...

Страница 19: ...nd lengths of the flue system For R2TND Nominal combustion products temperature 77 C Combustion products mass flow rate 10 75 g s Overheat combustion products temperature 90 C Minimum combustion produ...

Страница 20: ...use flue outlet duct length must be shortened with the same length Type C83x twin pipes flue system The boiler draws combustion air from outside via a separate supply pipe routed through the external...

Страница 21: ...h 140 19 6 69 2 DN 80 Flex square and rough 130 17 0 60 0 DN 80 Flex square and rough 120 12 2 43 0 DN 80 Star square and rough 140 47 5 167 8 DN 80 Star square and rough 120 33 3 117 9 Allowable flue...

Страница 22: ...e 60 100 with measurement point EKFGP4667 90 elbow 60 100 with measurement point DRMEEA60100BA 90 elbow 60 100 EKFGP4660 90 elbow 80 125 EKFGP4810 45 elbow 60 100 EKFGP4661 45 elbow 80 125 EKFGP4811 3...

Страница 23: ...om the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting 10 If after the venting the pressure decreases below 0 8 bar refill with water until t...

Страница 24: ...Back button INFORMATION Only qualified persons have access to servicing parameters The passwords needed to access service parameters are written in servicing instructions 5 Commissioning WARNING Only...

Страница 25: ...buttons together five seconds Sweeper mode will be deactivated and boiler will return to normal operation mode Sweeper mode also finishes automatically after 15 minutes 5 4 2 To commission the centra...

Страница 26: ......

Страница 27: ......

Страница 28: ...usland Our partners abroad Unsere Partner im Ausland Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani http...

Отзывы: