4 Installation

Installation manual

19

R2CND0 R2TND012~024A4AA
Wall-mounted condensing boiler
3P469346-4E – 2017.07

a

a

60/100 to 80/125 adapter

80/125 flue parts to be used are shown below:

a

b

c

d

e

f

a

80/125 wall terminal kit (type C13)

b

80/125 roof terminal kit (type C33)

c

90° elbow 80/125

d

45° elbow 80/125

e

30° elbow 80/125

f

Extension 80/125
L = 500-1000 mm

Type C43x (concentric flue system)

Several heat sources draw combustion air from the outside through
the annular gap of the room sealed balanced flue system and expel
flue  gas  to  the  outside  via  the  roof,  through  a  moisture-resistant
internal pipe.

The multi-served chimney is a system that is part of the building and
has a separate CE marking. The connection between the boiler and
the  shaft  and,  the  connection  between  the  boiler  and  the  air  intake
system must be obtained via ROTEX.

e

f

g

h

L

i

a b c

d

a

Tee flex boiler connection set 100 or 130

b

Extension 60 mm

c

Chimney connection 60/100

d

Elbow 60/100 90°

Optional:

e

90° elbow 60/100

f

45° elbow 60/100

g

Tee 60/100 with measurement point

h

30° elbow 60/100

i

Extension 60/100
L = 500-1000 mm

Maximum  allowable  length  of  the  flue  duct  up  to  common
chimney is 3  1 60/100 90° elbow.

In C43x type units, condensate flow into the unit is not allowed.

Type C63x (concentric flue system)

To  install  the  boiler  as  a  C63x  option  the  following  data  must  be
used  to  determine  the  correct  diameters  and  lengths  of  the  flue
system.

For R2TND*

▪ Nominal combustion products temperature: 77°C

▪ Combustion products mass flow rate: 10.75 g/s

▪ Overheat combustion products temperature: 90°C

▪ Minimum combustion products temperature: 20°C

▪ Maximum  allowable  pressure  difference  between  combustion  air

inlet and flue gas outlet (including wind pressures): 100 Pa

For R2CND*

▪ Nominal combustion products temperature: 93°C

▪ Combustion products mass flow rate: 11.48 g/s

▪ Overheat combustion products temperature: 100°C

▪ Minimum combustion products temperature: 20°C

▪ Maximum  allowable  pressure  difference  between  combustion  air

inlet and flue gas outlet (including wind pressures): 125 Pa

For R2CND* and R2TND*

▪ Minimum combustion products mass flow rate: 1.32 g/s

▪ CO

2

 content at nominal heat input: 9.0%

▪ Maximum allowable draught: 200 Pa

▪ The  boiler  must  be  connected  to  a  system  with  the  following

characteristics: T120 P1 W

▪ Maximum allowable temperature of combustion air: 50°C

▪ Maximum  allowable  recirculation  rate  under  wind  conditions  is

10%

▪ The  terminals  for  the  supply  of  combustion  air  and  for  the

evacuation  of  combustion  products  shall  not  be  installed  on
opposite walls of the building.

▪ Condensate flow into the unit is allowed.

Type C53x (twin pipes flue system)

Air  supply  and  flue  gas  discharge  from  /  to  atmosphere  in  areas  of
different pressure. The boiler draws combustion air from outside via
a horizontal pipe fitted to the external wall and expels flue gas to the
outside via the roof.

The terminals for the supply of combustion air and for the evacuation
of combustion products shall not be installed on opposite walls of the
building.

Содержание R2TND012A4AA

Страница 1: ...Installation manual Wall mounted condensing boiler English Installation manual Wall mounted condensing boiler R2CND024A4AA R2TND012A4AA R2TND018A4AA R2TND024A4AA...

Страница 2: ...is t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra n...

Страница 3: ...propriately disposed of in accordance with local and national regulations The components are easy to separate and the plastics are marked This allows the various components to be sorted for appropriat...

Страница 4: ...ommissioning repair configuration and service must be performed by qualified competent persons in accordance with local standards and regulations Incorrect installation of this unit may harm the user...

Страница 5: ...es It is controlled by the flow temperature sensor which is located at the outlet of the main heat exchanger This protection activates the boiler pump when the water temperature drops below 13 C and i...

Страница 6: ...rode p High limit thermostat q Fan r Return temperature sensor s Silencer t Automatic air vent pump u Water pressure sensor v By pass w Boiler pump x Domestic hot water flow sensor y Domestic hot wate...

Страница 7: ...max m h 0 12 0 46 0 12 0 69 0 12 0 96 0 12 0 96 Combustion products mass flow rate min max G20 g s 1 32 5 12 1 32 7 78 1 32 10 75 1 32 10 75 Combustion products mass flow rate min max G31 g s 1 23 4 7...

Страница 8: ...ters 50 C return temperature at heater inlet 4 Installation 4 1 To open the unit WARNING Only qualified competent persons are allowed to open the unit Certain actions explained in this document such a...

Страница 9: ...the current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake air must not include chemicals that may cause corrosion toxic gas format...

Страница 10: ...ght and related system charge pressure are given below h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0 bar 9 m 1 1 bar 10 m 1 2 bar 11 m 1 3 bar 12 m 1 4 bar 13 m 1 5 bar h h System water height m p System charge...

Страница 11: ...done to avoid discomfort of the user 4 7 Residual pump lift graph The residual pump lift graph shows the amount of pump lift mbar that remains for the central heating circuit 0 0 100 200 300 400 500 6...

Страница 12: ...ge while the gas line to the boiler is open see 5 3 To check for gas leakage on page 24 In case gas piping is adjacent to the wall and is to be connected to the gas pipe connection of the boiler with...

Страница 13: ...ny damage that may occur this way WARNING Use a dedicated power circuit Never use a power supply cable shared by another unit The unit runs on 230 V AC 50 Hz power A power cable is delivered with the...

Страница 14: ...nds that are sent with the unit must be assembled to the bottom sheet of the boiler in case connection of these options Below you can see the cable glands placement PG 9 PG 9 PG 7 PG 7 Holes on the bo...

Страница 15: ...012 024A4AA Wall mounted condensing boiler 3P469346 4E 2017 07 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Model R2CND024A4A...

Страница 16: ...ace Ext3 X1M Opentherm room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1M X4 X11 X12 Low voltage terminal strip X2M X1 X2 High voltage terminal strip 4 8 7 Guidel...

Страница 17: ...that products of combustion discharging from the terminal cannot re enter the building or other buildings through ventilators windows doors other sources of natural air infiltration or forced ventila...

Страница 18: ...it Optional c 45 elbow 60 100 d Extension 60 100 mm e Flat roof outlet kit f 90 elbow 60 100 g 45 elbow 60 100 h 30 elbow 60 100 i Extension 60 100 L 500 1000 mm Allowable flue length for C33x R2TND R...

Страница 19: ...nd lengths of the flue system For R2TND Nominal combustion products temperature 77 C Combustion products mass flow rate 10 75 g s Overheat combustion products temperature 90 C Minimum combustion produ...

Страница 20: ...use flue outlet duct length must be shortened with the same length Type C83x twin pipes flue system The boiler draws combustion air from outside via a separate supply pipe routed through the external...

Страница 21: ...h 140 19 6 69 2 DN 80 Flex square and rough 130 17 0 60 0 DN 80 Flex square and rough 120 12 2 43 0 DN 80 Star square and rough 140 47 5 167 8 DN 80 Star square and rough 120 33 3 117 9 Allowable flue...

Страница 22: ...e 60 100 with measurement point EKFGP4667 90 elbow 60 100 with measurement point DRMEEA60100BA 90 elbow 60 100 EKFGP4660 90 elbow 80 125 EKFGP4810 45 elbow 60 100 EKFGP4661 45 elbow 80 125 EKFGP4811 3...

Страница 23: ...om the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting 10 If after the venting the pressure decreases below 0 8 bar refill with water until t...

Страница 24: ...Back button INFORMATION Only qualified persons have access to servicing parameters The passwords needed to access service parameters are written in servicing instructions 5 Commissioning WARNING Only...

Страница 25: ...buttons together five seconds Sweeper mode will be deactivated and boiler will return to normal operation mode Sweeper mode also finishes automatically after 15 minutes 5 4 2 To commission the centra...

Страница 26: ......

Страница 27: ......

Страница 28: ...usland Our partners abroad Unsere Partner im Ausland Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani http...

Отзывы: