4.4.11 P4 Malfunction
The troubleshooting is same as the “IPM module protection”
4.4.12 J0 Malfunction
Malfunction conditions
When evaporator coil temperature is more than 60°C, the unit stops. It starts again only when the
evaporator coil temperature is less than 54°C
Possible causes
• Faulty evaporator coil temperature sensor
• Dirty heat exchanger
• Faulty fan
• Faulty PCB
J0 displayed
Evaporator high temperature protection
Is the compressor operating?
Yes
Is the outdoor ambient
temperature is higher than 30 ?
No
Correct the connection
No
Is the connection
between T2 and The
PCB is in working order?
Have T2 and T2B been
reversed?
Is the resistance of T2
normal according to
Appendix
1?
Replace the temperature sensor
No
Yes
Yes
Stop the unit
Yes
Is the air-outlet blocked?
Are the heat exchanger and
filter dirty?
Is the indoor fan running
normally?
No
Yes
Clean the air-outlet
Replace the indoor main
PCB
Clean the heat exchanger and filter
Yes
No
Yes
Refer to the solution for the
malfunction of the fan speed being out
of control . Find the cause and resolve
the problem
No
No
PART 6. TROUBLESHOOTING
Содержание J100Wi
Страница 1: ...LCAC R32 SERIES Tenji W Jato W Nevo W ENG Service manual ...
Страница 13: ...LCAC R32 Series 13 Service manual PART 2 INDOOR UNITS 1 5 2 Units 30 42K a Cooling b Heating ...
Страница 14: ...LCAC R32 Series 14 Service manual PART 2 INDOOR UNITS 1 5 3 Units 48 55K a Cooling b Heating ...
Страница 18: ...LCAC R32 Series 18 Service manual PART 2 INDOOR UNITS 1 10 1 Wiring diagram for T140Wi T160Wi ...
Страница 44: ...LCAC R32 Series 44 Service manual PART 2 INDOOR UNITS 3 10 FIELD WIRING ...
Страница 49: ...LCAC R32 Series 49 Service manual PART 3 OUTDOOR UNITS 3 4 Wiring diagrams T100Wo N100Wo J100Wo ...
Страница 131: ...LCAC R32 Series 131 Service manual NOTES ...
Страница 132: ...www rotenso pl email info rotenso pl Installer stamp ...