LCAC R32 Series
116
Service manual
4.4.18 P6/J6 Malfunction
Malfunction conditions
If the sampling voltage is not 5V, the LED displays a failure code.
Possible causes
• Wiring mistake
• Faulty over load protector
• System blockages
• Faulty outdoor PCB
J6 displayed
Low pressure protection
Are the low pressure
protector and main control
board wired properly?
Method: Disconnect the plug.
Measure the resistance of the
low pressure protector. If the
protector is normal the value is
o. Does a problem still exist?
Yes
Yes
Reconnect the low pressure
protector and main control
board
Replace outdoor main board.
Does a problem still exist?
No
Replace low pressure protector
No
Is the low
pressure protector
broken?
Is the outdoor ambient
temperature too low?
No
Stop the unit
Yes
Open the valve core of the
high pressure valve
No
Is the valve core of the
high pressurevalve fully
opened?
Is the indoor fan running
properly in cooling mode?
Refer to the solution to the malfunction
of fan speed being out of control. Find
the cause and resolve the problem.
No
Yes
Yes
No
Check whether the refrigerant
system is functioning properly.
When the lvel of refrigerant is not
sufficient, doe the system function
properly after more refrigerant is
added?
No
PART 6. TROUBLESHOOTING
Содержание J100Wi
Страница 1: ...LCAC R32 SERIES Tenji W Jato W Nevo W ENG Service manual ...
Страница 13: ...LCAC R32 Series 13 Service manual PART 2 INDOOR UNITS 1 5 2 Units 30 42K a Cooling b Heating ...
Страница 14: ...LCAC R32 Series 14 Service manual PART 2 INDOOR UNITS 1 5 3 Units 48 55K a Cooling b Heating ...
Страница 18: ...LCAC R32 Series 18 Service manual PART 2 INDOOR UNITS 1 10 1 Wiring diagram for T140Wi T160Wi ...
Страница 44: ...LCAC R32 Series 44 Service manual PART 2 INDOOR UNITS 3 10 FIELD WIRING ...
Страница 49: ...LCAC R32 Series 49 Service manual PART 3 OUTDOOR UNITS 3 4 Wiring diagrams T100Wo N100Wo J100Wo ...
Страница 131: ...LCAC R32 Series 131 Service manual NOTES ...
Страница 132: ...www rotenso pl email info rotenso pl Installer stamp ...