4.4.7 F4 Malfunction
Malfunction conditions
Main PCB chip does not receive feedback from EEPROM chip
Possible causes
• Installation mistakes
• Faulty PCB
Yes
Replace the outdoor main PCB
Power off, then restart the
unit 2 minutes later. Does a
problem still exist?
Outdoor EEPROM malfunction
F4-Display
4.4.8 F5 Malfunction
The same as E3 in indoor unit.
EEPROM:
An electrically erasable programmable read-only memory whose contents can be erased and reprogrammed
using a pulsed voltage.
4.4.9 P0 Malfunction
Malfunction conditions
When the voltage signal te IPM sends to compressor drive chip is not normal, the LED displays “P0”
and the unit turns off.
Possible causes
• Wiring mistakes
• Faulty IPM board
• Faulty outdoor fan assembly
• Compressor malfunction
• Faulty outdoor PCB