LCAC R32 Series
69
Service manual
5.2.5 Insulate the copper pipe
• Before test operation, the joint parts should not be heat insulated.
5.2.6 Flare the pipe
• Insert a flare nut into the pipe before flaring the pipe
• According to the following table to flare the pipe
Pipe diameter
Flare dimension A (mm)
Flare Shape
Min
Max
1/4” (6.35)
8.3
8.7
R0.4~0.8
A
45°
90
°
4
-+
3/8” (9.52)
12.0
12.4
1/2” (12.7)
15.4
15.8
5/8” (15.9)
18.6
19.1
3/4” (19)
22.9
23.3
• After flared the pipe, the opening part must be seal by end cover or adhesive tape to avoid duct or exogenous
impurity come into the pipe.
5.2.7 Drill holes if the pipes need to pass the wall.
5.2.8 According to the field condition to bend the pipes so that it can pass the wall smoothly.
5.2.9 Bind and wrap the wire together with the insulated pipe if necessary.
5.2.10 Set the wall conduit
5.2.11 Set the supporter for the pipe.
5.2.12 Locate the pipe and fix it by supporter
• For horizontal refrigerant pipe, the distance between supporters should not be exceed 1m.
• For vertical refrigerant pipe, the distance between supporters should not be exceed 1.5m.
5.2.13 Connect the pipe to indoor unit and outdoor unit by using two spanners.
• Be sure to use two spanners and proper torque to fasten the nut, too large torque will damage the bellmouthing,
and too small torque may cause leakage. Refer the following table for different pipe connection.
Pipe diameter
Torque
Sketch map
(kgf.cm)
(N.cm)
1/4" (6.35)
144~176
1420~1720
3/8" (9.52)
333~407
3270~3990
1/2" (12.7)
504~616
4950~6030
5/8" (15.9)
630~770
6180~7540
3/4" (19)
990~1210
9270~11860
PART 4. INSTALLATION
Содержание J100Wi
Страница 1: ...LCAC R32 SERIES Tenji W Jato W Nevo W ENG Service manual ...
Страница 13: ...LCAC R32 Series 13 Service manual PART 2 INDOOR UNITS 1 5 2 Units 30 42K a Cooling b Heating ...
Страница 14: ...LCAC R32 Series 14 Service manual PART 2 INDOOR UNITS 1 5 3 Units 48 55K a Cooling b Heating ...
Страница 18: ...LCAC R32 Series 18 Service manual PART 2 INDOOR UNITS 1 10 1 Wiring diagram for T140Wi T160Wi ...
Страница 44: ...LCAC R32 Series 44 Service manual PART 2 INDOOR UNITS 3 10 FIELD WIRING ...
Страница 49: ...LCAC R32 Series 49 Service manual PART 3 OUTDOOR UNITS 3 4 Wiring diagrams T100Wo N100Wo J100Wo ...
Страница 131: ...LCAC R32 Series 131 Service manual NOTES ...
Страница 132: ...www rotenso pl email info rotenso pl Installer stamp ...