LCAC R32 Series
17
Service manual
2.9 THE SPECIFICATION OF POWER
PART 2. INDOOR UNITS
Model(Btu/h)
18000~24000
36000
36000
48000~60000
Indoor power
Phase
1-phase
1-phase
1-phase
-
Frequency and Voltage
220-240V, 50Hz
220-240V, 50Hz
220-240V, 50Hz
-
Power wiring (mm
2
)
3×1.0
3×1.0
3×1.0
-
Circuit breaker/Fuse (A)
15/10
15/10
15/10
-
Indoor power
Phase
1-phase
1-phase
3-phase
3-phase
Frequency and Voltage
220-240V, 50Hz
220-240V, 50Hz
380-415V, 50Hz
380-415V, 50Hz
Power wiring (mm
2
)
3×2.5
3×4.0
5×2.5
5×2.5
Circuit breaker/Fuse (A)
25/20
40/30
25/20
30/25
Indoor/Outdoor Connecting Wiring
(Weak Electric Signal) (mm
2
)
2×0.2
2×0.2
2×0.2
2×0.2
Indoor/Outdoor Connecting Wiring
(Strong Electric Signal) (mm
2
)
-
-
-
3×1.0
1.10 FIELD WIRING
1.10.1 Wiring diagram for T50Wi, T70Wi, T100Wi
Содержание J100Wi
Страница 1: ...LCAC R32 SERIES Tenji W Jato W Nevo W ENG Service manual ...
Страница 13: ...LCAC R32 Series 13 Service manual PART 2 INDOOR UNITS 1 5 2 Units 30 42K a Cooling b Heating ...
Страница 14: ...LCAC R32 Series 14 Service manual PART 2 INDOOR UNITS 1 5 3 Units 48 55K a Cooling b Heating ...
Страница 18: ...LCAC R32 Series 18 Service manual PART 2 INDOOR UNITS 1 10 1 Wiring diagram for T140Wi T160Wi ...
Страница 44: ...LCAC R32 Series 44 Service manual PART 2 INDOOR UNITS 3 10 FIELD WIRING ...
Страница 49: ...LCAC R32 Series 49 Service manual PART 3 OUTDOOR UNITS 3 4 Wiring diagrams T100Wo N100Wo J100Wo ...
Страница 131: ...LCAC R32 Series 131 Service manual NOTES ...
Страница 132: ...www rotenso pl email info rotenso pl Installer stamp ...