LCAC R32 Series
90
Service manual
N
Display
Remark
19
Condenser pipe temperature of #1 indoor
unit
If the temperature is lower than 0°C, the digital display shows “0”. If the
temperature is higher than 70°C, the digital display shows “70.”
If the capacity demand is 0, the digital display shows “0”.
If the indoor unit is not connected, the digital display shows:
“
”(heating T2, cooling T2B)
20
Condenser pipe temperature of #2 indoor
unit
21
Reserved
22
#1 Indoor unit capacity demand code
Actual data*HP*10
If a capacity demand code is higher than 99, the digital display shows single and
double digits.
For example, if the digital display reads “5.0”, the capacity demand is 15.
If the digital display shows “60”, the capacity demand is 6.0.
If the indoor unit is not connected, the digital display shows: “
”
23
#2 Indoor unit capacity demand code
24
Reserved
25
Indoor room temperature of #1 indoor unit
If the temperature is lower than -9°C, the digital display shows “9”.
If the temperature is higher than 70°C, the digital display shows “70”.
If the capacity demand is 0, the digital display shows “0”.
If the indoor unit is not connected, the digital display shows: “
”
26
Indoor room temperature of #2 indoor unit
If the temperature is lower than 0°C, the digital display shows “0”.
If the temperature is higher than 70°C, the digital display shows “70”.
If the capacity demand is 0, the digital display shows “0”.
If the indoor unit is not connected, the digital display shows: “
””
27
Average of indoor room temperature
If the temperature is lower than 0°C, the digital display shows “0”.
If the temperature is higher than 70°C, the digital display shows “70”
28
Shut down cause
Refer to Appendix
29
T2B of #1 indoor unit
If the temperature is lower than -9°C, the digital display shows “9”.
If the temperature is higher than 70°C, the digital display shows “70”.
If the capacity demand is 0, the digital display shows “0”.
If the indoor unit is not connected, the digital display shows: “
”
30
T2B of #2 indoor unit
If the temperature is lower than 0°C, the digital display shows “0”.
If the temperature is higher than 70°C, the digital display shows “70”.
If the capacity demand is 0, the digital display shows “0”.
If the indoor unit is not connected, the digital display shows: “
”
Appendix
Shutdown Causes
Code
Frequency limit caused by current
1
Frequency limit caused by T2 in cooling
2
Frequency limit caused by T2 in heating
3
Preset temperature reached
4
Frequency limit caused by T4
5
Defrosting
6
Mode switching
7
High discharge temperature protection
9
High evaporator coil temperature T2 protection
10
Evaporator low temperature T2 protection
11
Condenser high temperature T3 protection
12
Low indoor room temperature protection in drying mode
13
PART 5. ELECTRICAL CONTROL SYSTEM
Содержание J100Wi
Страница 1: ...LCAC R32 SERIES Tenji W Jato W Nevo W ENG Service manual ...
Страница 13: ...LCAC R32 Series 13 Service manual PART 2 INDOOR UNITS 1 5 2 Units 30 42K a Cooling b Heating ...
Страница 14: ...LCAC R32 Series 14 Service manual PART 2 INDOOR UNITS 1 5 3 Units 48 55K a Cooling b Heating ...
Страница 18: ...LCAC R32 Series 18 Service manual PART 2 INDOOR UNITS 1 10 1 Wiring diagram for T140Wi T160Wi ...
Страница 44: ...LCAC R32 Series 44 Service manual PART 2 INDOOR UNITS 3 10 FIELD WIRING ...
Страница 49: ...LCAC R32 Series 49 Service manual PART 3 OUTDOOR UNITS 3 4 Wiring diagrams T100Wo N100Wo J100Wo ...
Страница 131: ...LCAC R32 Series 131 Service manual NOTES ...
Страница 132: ...www rotenso pl email info rotenso pl Installer stamp ...