112
Service manual
4.4.14 J2 Malfunction
Malfunction conditions
When the compressor discharge temperature (T5) is more than 115°C for 10 seconds, the
compressor will stop and not restart until T5 is less than 90°C.
Possible causes
• Refrigerant leakage
• Wiring mistake
• Faulty discharge temperature sensor
• Faulty outdoor PCB
J2 displayed
Temperature protection of
compressor discharge
Is the compressor discharge
temperature more than 115°C
?
Are the compressor
discharge
temperature
sensor and PCB connected
properly according to the
wiringdiagrams?
Measure the resiistance vallue
of compressor diischarge
temp. sensor. If the vallue iis
not normall,,refer to the
Appendix
2. Does a problem stil
exist?
No
Yes
Yes
No
Correct the wiring connection
Stop the leak and add refrigerant
No
Replace the compressor discharge temp. sensor
No
Yes
Repllace hiigh pressure vallve assy
Yes
No
Repllace outdoor maiin PCB.
Does a probllem stiilll exiist?
Is refrigerant leaking?
PART 6. TROUBLESHOOTING
Содержание J100Wi
Страница 1: ...LCAC R32 SERIES Tenji W Jato W Nevo W ENG Service manual ...
Страница 13: ...LCAC R32 Series 13 Service manual PART 2 INDOOR UNITS 1 5 2 Units 30 42K a Cooling b Heating ...
Страница 14: ...LCAC R32 Series 14 Service manual PART 2 INDOOR UNITS 1 5 3 Units 48 55K a Cooling b Heating ...
Страница 18: ...LCAC R32 Series 18 Service manual PART 2 INDOOR UNITS 1 10 1 Wiring diagram for T140Wi T160Wi ...
Страница 44: ...LCAC R32 Series 44 Service manual PART 2 INDOOR UNITS 3 10 FIELD WIRING ...
Страница 49: ...LCAC R32 Series 49 Service manual PART 3 OUTDOOR UNITS 3 4 Wiring diagrams T100Wo N100Wo J100Wo ...
Страница 131: ...LCAC R32 Series 131 Service manual NOTES ...
Страница 132: ...www rotenso pl email info rotenso pl Installer stamp ...