Rosemount Model 8732C Integral Mount Magnetic Flowmeter System
4-12
NOISE REDUCTION
Damping
Damping allows selection of a response time, in seconds, to a step change in
flow rate. It is most often used to smooth fluctuations in output.
Coil Frequency
Coil Frequency allows pulse-rate selection of the flowtube coils.
6 Hz
The standard coil pulse mode is 6 Hz, which is sufficient for
nearly all applications.
30 Hz
If the process fluid causes a noisy or unstable output, increase the coil
pulse mode to 30 Hz. If the 30 Hz mode is selected, perform the Auto
Zero function as shown below.
Auto Zero
Auto Zero initializes the transmitter for use with the 30 Hz coil drive
mode only. Run this function only with the transmitter and flowtube
installed in the process. The flowtube must be filled with process fluid
at zero flow. Before running the auto zero function, be sure the coil
drive mode is set to 30 Hz.
Set the loop to manual if necessary. Then, begin the auto zero procedure. The
transmitter completes the procedure automatically in about two minutes. A
symbol appears in the lower right-hand corner of the display to indicate that
the procedure is running.
Low Flow Cutoff
Low Flow Cutoff allows you to specify the flow rate, between 0.001
and 1.0 foot per second, below which the outputs are driven to zero flow.
The units format for low flow cutoff cannot be changed. It is always
displayed as feet per second regardless of the format selected. The low
cutoff value applies to both forward and reverse flows.
Signal Processing
Signal Processing is a software algorithm that examines the quality
of the electrode signal against user-specified tolerances. If spurious
noise spikes are detected, they are automatically rejected. There are
three parameters associated with this function:
• Number of samples (0 to 125)
• Maximum percent limit (0 to 100 percent of running average)
• Time limit (0 to 256 seconds)
HART Fast Keys
1, 3, 7
LOI
Basic Setup
HART Fast Keys
1, 4, 4, 3
LOI
Detailed Setup
HART Fast Keys
1, 2, 4, 4
LOI
Transmitter Trim
HART Fast Keys
1, 4, 4, 1
LOI
Detailed Setup
HART Fast Keys
1, 4, 4
LOI
Detailed Setup
Содержание 8732C
Страница 1: ...Model 8732C Integral Mount Magnetic Flowmeter System 00809 0100 4725 English Rev BB ...
Страница 2: ......
Страница 4: ......
Страница 10: ...vi ...
Страница 39: ...2 27 Installation ...
Страница 40: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System 2 28 ...
Страница 66: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System 4 20 ...
Страница 74: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System 5 8 ...
Страница 80: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System 6 6 ...
Страница 96: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System 8 6 ...
Страница 108: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System A 12 ...
Страница 116: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System B 8 ...