Rosemount Model 8732C Integral Mount Magnetic Flowmeter System
C-4
This scenario is that of a typical non-noisy flow. The input flow
signal is within the percent limit tolerance band, therefore
qualifying itself as a good input. In this case the new input is
added directly into the running average and is passed on as a part
of the average value to the output.
This signal is outside the tolerance band and therefore is held in
memory until the next input can be evaluated. The running
average is provided as the output.
The previous signal currently held in memory is simply rejected
as a noise spike since the next flow input signal is back within the
tolerance band. This results in complete rejection of noise spikes
rather than allowing them to be “averaged” with the good signals
as occurs in the typical analog damping circuits.
As in Number 2 above, the input is outside the tolerance band.
This first signal is held in memory and compared to the next signal.
The next signal is also outside the tolerance band (in the same
direction), so the stored value is added to the running average
as the next input and the running average begins to slowly
approach the new input level.
To avoid waiting for the slowly incrementing average value to catch
up to the new level input, a shortcut is provided. This is
the “time limit” parameter. The user can set this parameter
to eliminate the slow ramping of the output toward the new
input level.
When Should Signal
Processing Be Used?
The Model 8732C offers three separate functions that can be used in
series for improving a noisy output. The first step is to toggle the coil
drive to the 30 Hz mode and initialize with an auto zero. If the output is
still noisy at this stage, signal processing should be actuated and, if
necessary, tuned to match the specific application. Finally, if the signal
is still too unstable, the traditional damping function can be used.
Содержание 8732C
Страница 1: ...Model 8732C Integral Mount Magnetic Flowmeter System 00809 0100 4725 English Rev BB ...
Страница 2: ......
Страница 4: ......
Страница 10: ...vi ...
Страница 39: ...2 27 Installation ...
Страница 40: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System 2 28 ...
Страница 66: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System 4 20 ...
Страница 74: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System 5 8 ...
Страница 80: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System 6 6 ...
Страница 96: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System 8 6 ...
Страница 108: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System A 12 ...
Страница 116: ...Rosemount Model 8732C Integral Mount Magnetic Flowmeter System B 8 ...