Device functions
Version 1
RES-5009
Page 53
Part 3 of 3: Error messages (warnings)
NOTE:
The specified error messages are first output as warnings:
• Actual value output changes between two values
• Alarm-LED blinks slowly
• Alarm relay is not active
After activation of the START signal, the output occurs as a fault
• Actual value output does not change any more, see bold italic values
• Alarm LED lights up continuously
• Alarm relay is active
Error no.
Actual
value
outp.
Voltg. [V]
Cause
Measure during initial
startup
Measure during
machine operation,
heating element not
changed
10
111
6.66
10
Current signal incorrect,
Calibration not possible
Error range
,
Check configuration
Error ranges
(“Loose contact”)
11
112
7.33
10
Voltage signal incorrect,
Calibration not possible
Error range
,
Check configuration
Error ranges
(“Loose contact”)
12
113
8.00
10
Voltage/current signal incor-
rect,
Calibration not possible
Error ranges
,
Check configuration
Error ranges
(“Loose contact”)
13
114
8.66
10
Temperature fluctuates,
Calibration not possible
Perform
AUTOCAL
and/or
Error ranges
(“Loose contact”)
Perform
AUTOCAL
and/or
Error ranges
(“Loose contact”)
115
Ext. calibration temperature
too high,
Calibration not possible
Perform
AUTOCAL
with
ext. calibration temp.
≤40 °C
Perform
AUTOCAL
with
ext. calibration temp.
≤40 °C
116
Ext. calibration temperature
fluctuates,
Calibration not possible
Perform
AUTOCAL
with
stable ext. calibration
temperature
Perform
AUTOCAL
with
stable ext. calibration
temperature