Mounting and Installation
Page 14
RES-5009
Version 1
3. Wiring of the system in accordance with the regulations in section 7.3 "Mains connection" on page 16,
section 7.6 "Wiring diagram (standard)" on page 19 and the ROPEX application report. The specifications in
section 7.2 "Installation notes" on page 15 must also be observed.
Cables that are connected to control or measurement connections may only run within the building.
4. During installation, a circuit breaker with max. 10 A must be provided, e. g.:
- circuit breaker in accordance with EN 60898 (characteristic B, C, D, K or Z)
- circuit breaker in accordance with UL489 (*) (characteristic B, C, D, K or Z)
- protective fuse gG in accordance with IEC 60269
- protective fuse “Class CC” or “Class J” in accordance with UL 248 (*)
The circuit breakers marked with (*) must be used in installations falling under the UL regulations.
If the specified circuit breaker is not sufficient for the welding application, two separate circuit breakers must be
provided for the controller and the welding application (
ROPEX application report).
The circuit breaker must be located in the immediate vicinity of the device.
In the ROPEX application report, the smallest possible specification for this circuit breaker is specified based
on the calculated currents. If the protective device is dimensioned differently, the current carrying capacity of
the components used (e. g. cable, impulse transformer, etc.) must be adjusted accordingly.
5. A disconnect device must be provided during installation. The disconnect device must be properly marked as
part of the system and attached in an easily accessible position.
If a circuit breaker is used, it can take over the function of the disconnect device.
6. Connect the RESISTRON
®
Temperature Controller RES-5009 to the CAN network with a SUB-D9 connection
cable according to specification CANopen CiA 303/1.
CAUTION
Check all connection terminals of the system and the terminals for the coil wires on the impulse
transformer – that they are seated firmly.
7. Check the wiring in accordance with the applicable national and international installation and setup require-
ments.