Device functions
Page 50
RES-5009
Version 1
Part 1 of 3: Error messages (faults)
NOTE:
The specified error messages are output as faults:
• Actual value output displays constant error voltage
• Alarm LED lights up continuously
• Alarm relay is active
Error no.
Actual
value
outp.
Voltg. [V]
Cause
Measure during initial
startup
Measure during
machine operation,
heating element not
changed
1
101
0.66
Current signal missing
Error area
Error area
2
102
1.33
Voltage signal missing
Error area
Error area
3
103
2.00
Voltage and current signals
missing
Error area
Error areas
4
107
2.66
Temperature drop
Error ranges
(“Loose contact”)
Error ranges
(“Loose contact”)
108
Temperature spike
307
Temperature too low, leave
the tolerance band
(
Chap. 9.4.7)
Check the dimensioning
of the pulse transformer,
Check heat removal
through the sealing pro-
cess,
Verify application through
sealing tests
-
308
Temperature too high, leave
tolerance band
(
Chap. 9.4.7)
309
Temperature too low, toler-
ance band not reached
(
Chap. 9.4.7)
310
Temperature too high, toler-
ance band not reached
(
Chap. 9.4.7)
5
201
3.33
Line frequency missing/fluc-
tuates
Check line:
Line frequency
Harmonic waves
Voltage fluctuations
Check line:
Line frequency
Harmonic waves
Voltage fluctuations
202
Line frequency too large/
fluctuates
203
Line frequency too small/
fluctuates
6
304
4.00
Heat-up time too long
(
chap. 9.4.8)
Perform
RESET
Check the dimensioning
of the pulse transformer,
Verify the parametrised
heating time,
Check lines and contacts
Perform
RESET
Check lines and con-
tacts,
Verify the sealing pro-
cess