Startup and operation
Version 1
RES-5009
Page 21
8
Startup and operation
8.1
Device view
8.2
Device configuration
8.2.1
Configuration of the ranges for secondary voltage and current
The ranges for secondary voltage and current are configured automatically when automatic calibration
(AUTOCAL) is carried out. Configuration takes place in the voltage range of 0.4 VAC up to 120 VAC and in the
current range from 30 A to 500 A. If voltage and/or current is outside the allowed range, a detailed error message
is output by the controller (
section 9.15 "Error messages" on page 49).
For secondary currents I
2
less than 30 A, the secondary high-current line must be guided 2 times (or several times)
through the transformer PEX-W4 or PEX-W5 (
ROPEX application report).
NOTE
The controller must be switched off to configure the coding switch and the slide switch.
Connection terminals
Display LEDs
Coding and
Nameplate
Terminal plan
Slide switch
USB interface
CAN
Connection socket
2x