Controller functions
Page 34
RES-409
Version 1
10.3.1 Temperature setting (set point selection)
Up to four different set points can be permanently stored in the RES-409. The stored values are not lost if the
power supply is interrupted. They can be reloaded on request. It is possible to switch between preheat and main
heat, for instance, or to increase the temperature to a particular set point gradually in a series of steps ("ramp")
simply by programming the set points accordingly. The maximum settable set point T
max
is dependent on the
selected temperature range (see CAN message address 8 and CAN message address 4, value 12). Temperature
ranges of 200°C, 300°C, 400°C and 500°C, can be defined here.
All set points greater than T
max
are rejected by RES-409 controllers manufactured up to January 2007. In this
case, the last stored set point remains valid.
The set point is limited to T
max
and subsequently stored on controllers manufactured as of February 2007. If "Alloy/
range" (CAN message address 8) is set to "Variable" (value 11), T
max
is determined by the selected temperature
range (CAN message address 13
h
) and the value stored under "Maximum set point" (CAN message B).
The set point selected for the heatsealing temperature must be greater than 40°C. If not, the heatsealing band is
not heated when the start/stop command is activated.
10.3.2 START / STOP command "START" signal
A "START" command or a "START" signal is rejected ("HEAT" LED blinks fast) if the "AUTOCAL"
function is running or a "RESET" command is active.
The fault output is switched if a "START" command (or the "START" signal) is activated while a warning message
with error codes 8…12 (as of February 2007 also: 104…106, 111…114, 211, 302, 303) is displayed
(
section 10.16 "Error messages" on page 52). The heatsealing band is no longer heated.
By means of the CAN protocol:
000F
0
1
Temperature diagnosis: OFF
Temperature diagnosis: ON
(
section 10.10 "Temperature diagnosis (as of February 2007)" on page 48)
0010
0…99
Temperature diagnosis delay in 0.1s
(
section 10.10 "Temperature diagnosis (as of February 2007)" on page 48)
0011
0…999
Heatup timeout (0 = OFF) in 0.1s
(
section 10.11 "Heatup timeout (as of February 2007)" on page 49)
0012
17…30
Measuring impulse length in 0.1ms
(
section 10.7 "Measuring impulse length (as of February 2007)" on page 45)
0013
0
1
2
AUTOCOMP: OFF
AUTOCOMP: ON
AUTOCOMP: AUTO (as of software revision 102)
(
section 10.8 "Automatic phase compensation (AUTOCOMP, as of February
0014
0
1
2
3
Temperature range 200°C
Temperature range 300°C
Temperature range 400°C
Temperature range 500°C
(applies if address 0008 contained the value 11 (dec))
F002
Any
All parameters have factory setting (
section 11 "Factory settings" on page 58)
Address
(hex)
Value
(dec)
Meaning
!