4. Install the module:
a) in the O-R1, O-R2 O-R3 housing on the pins included in the kit,
b) in the GSM transmitter housings or control panel housing on the self adhesive pins
supplied with the module,
c) in the information and communication systems housing using the clip securing the
DIN housing to the assembly bus.
4. Connect the optional additional modules: VSR-2, PSR, PSR-RF
5. Connect the wires to the appropriate module connectors.
6. Connect the external antenna to the FME-F connector.
7. Switch on the module power supply.
8. Connect the cable between the service computer and the RS TTL socket (RS232, USB).
9. Configure the module according to requirements.
10. Perform tests.
11. Disconnect the cable from the RS TTL connector.
Remarks:
•
Observe all possible precautionary measures against static discharge to protect
the electronic components.
•
Do not switch on the power supply when the external antenna is not connected.
•
When installing in O-R2, O-R3 and other dedicated housings, intended for using
with the mains power supply (with transformer), do not connect the N (“zero”)
cable to the PE grounding clamp of the 230V AC mains power supply. Connecting
the N cable to the PE clamp may damage the electronic components, as GND is
then directly connected to PE! If there is no separate grounding cable provided,
the clamp should be left disconnected.
•
In pt. 2.b pins should be inserted in the module PCB board (4 pcs.) Remove the
protective foil from the adhesive layer, place on the inside degreased housing
surface and press lightly.
4.2. CONNECTING THE VOICE SYNTHETIZER OR AUDIO MODULE.
The MGSM 5.0/5.0-PS module has a VSR socket intended for connecting the VSR-2,
ARA and the MC-1 audio or other (e.g. utilized in CCTV) voice synthesizer modules,
provisioned for listening in on the object.
●
The voice synthesizer can record and relay a voice command when an event (alarm) occurs
in the system. Replay is performed automatically after establishing voice communication. The
message is repeated cyclically until the connection is terminated. The voice synthesizer
should be connected directly to the VSR connector and the message recorded after the power
supply is switched on (built in microphone).
The message is stored even after the power supply is disconnected (disconnected
synthesizer).The synthesizer has got a MINIJACK output for listening to the recording.
●
Listening in on the object can be accomplished with the AMR-1 module, when the alarm is
triggered or when a voice message is established (connecting with the module from