Page 48
OCR section
Address
Attribute
Measurement
Format
Descriptions
Inverse OCR
43201
R/W
Function
UINT16
Refer to “Value Table T9”
43202
R/W
Selected Curve
UINT16
Refer to “Value Table T3”
43203
R/W
Tap (Pickup value)
S2 UINT16 0.50 - 12.00 / 0.01 A
43204
R/W
Level (Multiplier)
S2 UINT16 0.05 - 1.20 / 0.01
Definite time[Instantaneous] OCR
43205
R/W
Function
UINT16
Refer to “Value Table T9”
43206
R/W
Tap (Pickup value)
S2 UINT16 1.00 - 99.99 / 0.01 A
43207
R/W
Delay
S2 UINT16 0.05 - 60.00 / 0.01 sec
Instantaneous OCR
†
43208
R/W
Function
UINT16
Refer to “Value Table T9”
43209
R/W
Tap (Pickup value)
S1 UINT16 2.0 - 100.0 / 0.1 A
43210
R/W
OCR Save Request
(Save Address : 43201 - 43209)
UINT16
0x00FF = Save Request
0x0000 = Not Save
†
Supported in F/W version 5.0 or lower. From Version 5.0, if the definite time of the OCR Delay is set to 0.05
sec, the instantaneous function is available.
NSOCR section
Address
Attribute
Measurement
Format
Descriptions
Inverse NSOCR
43211
R/W
Function
UINT16
Refer to “Value Table T9”
43212
R/W
Selected Curve
UINT16
Refer to “Value Table T13”
43213
R/W
Tap (Pickup value)
S2 UINT16 0.10 - 4.00 / 0.01 A
43214
R/W
Level (Multiplier)
S2 UINT16 0.05 - 1.20 / 0.01
Instantaneous[Definite time] NSOCR
43215
R/W
Function
UINT16
Refer to “Value Table T9”
43216
R/W
Tap (Pickup value)
S2 UINT16 0.10 - 50.00 / 0.01 A
43217
R/W
Delay
S2 UINT16 0.05 - 60.00 / 0.01 sec
•••
R
Reserved
UINT16
•••
43220
R/W
NSOCR Save Request
(Save Address : 43211 - 43217)
UINT16
0x00FF = Save Request
0x0000 = Do Not Save