Page 44
Digital Input Setup section
Address
Attribute
Measurement
Format
Descriptions
43051
R/W
DI delay time
S1 UINT16 0.1 - 10.0 / 0.1 sec
43052
R
Reserved
UINT16
43053
R/W
Alarm Reset
UINT16
Refer to
“Value Table T11”
43054
R/W
Fault Reset
UINT16
Refer to “Value Table T11”
43055
R/W
UVR Restoration Control
UINT16
Refer to “Value Table T11”
43056
R/W
Remote Mode
UINT16
Refer to “Value Table T11”
43057
R/W
Cold Load Pickup
UINT16
Refer to “Value Table T11”
43058
R/W
CB Close Block
UINT16
Refer to “Value Table T11”
43059
R/W
Digital Input Save Request
(Save Address :
43051, 43053 - 43058, 43060 - 43063
UINT16
0x00FF = Save Request
0x0000 = Do Not Save
43060
R/W
CB Open
UINT16
Refer to “Value Table T11”
43061
R/W
Alarm Output
UINT16
Refer to “Value Table T11”
43062
R/W
UVR Reset
UINT16
For restoration of UVR and auto
reset
Refer to “Value Table T11”
43063
R/W
CB status recognition of auxiliary B contact
input
UNIT16
0 : Do Not select
10 : Use DIN10 as input
•••
Invalid
UINT16
•••
43070
Invalid
UINT16