Page 28
40104
R
Voltage average
UINT16
VSA[40109]
40105
R
Line Voltage ab
UINT16
VSA[40109]
40106
R
Line Voltage bc
UINT16
VSA[40109]
40107
R
Line Voltage ca
UINT16
VSA[40109]
40108
R
Line Voltage average
UINT16
VSA[40109]
40109
R
Voltage scale
UINT16
40110
R
Current a
UINT16
VSB[40118]
40111
R
Current b
UINT16
VSB[40118]
40112
R
Current c
UINT16
VSB[40118]
40113
R
Current average
UINT16
VSB[40118]
40114
R
Fundamental Current a
UINT16
VSB[40118]
40115
R
Fundamental Current b
UINT16
VSB[40118]
40116
R
Fundamental Current c
UINT16
VSB[40118]
40117
R
Fundamental Current average
UINT16
VSB[40118]
40118
R
Current Scale
UINT16
40119
R
kW a
INT16
VSB[40122]
40120
R
kW b
INT16
VSB[40122]
40121
R
kW c
INT16
VSB[40122]
40122
R
kW Scale
UINT16
40123
R
Total kW
INT16
VSB[40124]
40124
R
Total kW Scale
UINT16
40125
R
kVAR a
INT16
VSB[40128]
40126
R
kVAR b
INT16
VSB[40128]
40127
R
kVAR c
INT16
VSB[40128]
40128
R
kW Scale
UINT16
40129
R
Total kVAR
INT16
VSB[40130]
40130
R
Total kVAR Scale
UINT16
40131
R
kVA a
INT16
VSB[40134]
40132
R
kVA b
INT16
VSB[40134]
40133
R
kVA c
INT16
VSB[40134]
40134
R
Phase kVA Scale
UINT16
40135
R
Total kVA
INT16
VSB[40136]
40136
R
Total kVA Scale
UINT16
40137
R
PF a
INT16
x0.001
40138
R
PF b
INT16
x0.001
40139
R
PF c
INT16
x0.001
40140
R
Total PF
INT16
x0.001
40141
R
Frequency
UINT16
x0.01
40142-
40143
R/W
kWh net
1
[kWh received
–
kWh delivered]
INT32
x1
Refer to
”
Data Format
s”
40144-
40145
R/W
kVARh net
1
[kVARh received
–
kVARh delivered]
INT32
x1
Refer to
”
Data Format
s”
40146-
40147
R/W
kVAh
INT32
x1
Refer to
”
Data Format
s”
†
Refer to
“
Measurement Value Calculation
”
1
kWh/kVARh net indicates the value obtained by subtracting Received energy from Delivered energy.