Page 14
Chapter 2 Communication Wiring/Setup
Communication Wiring
Communication Ports on the Relay
Item
Description
Port name
Ta[TRX+], Tb[TRX-]
Connector type
Screw-type terminal [Pluggable]
Wire specs
1.25 to 3.5 mm
2
[24 to 14 AWG], Shielded twisted pair
Communication cable length
1219m[4000ft]
Maximum number of connected
devices per bus
32
Note
It is recommended to use a cable that complies with the UL2919 standard.
Communication LED Indicator
The Comm LED on the front of Accura 7500 blinks yellow when it transmits data.