Page 45
Digital Output Setup section
Address
Attribute
Measurement
Format
Descriptions
43071
R/W
CB Operation Delay Time
UINT16
1 - 10 / 1 sec
43072
R/W
CB Open, Close Seal In Time
S1 UINT16 0.0 - 3.0 / 0.1 sec
43073
R/W
Alarm Output Type
UINT16
Refer to “Value Table T12”
43074
R/W
Alarm Output Dwell Time
UINT16
1 - 600 / 1sec
43075
R/W
Aux. DO1 Relay Type
UINT16
Refer to “Value Table T12”
43076
R/W
Aux. DO1 Dwell Time
UINT16
1 - 600 / 1sec
43077
R/W
Aux. DO2 Relay Type
UINT16
Refer to “Value Table T12”
43078
R/W
Aux. DO2 Dwell Time
UINT16
1 - 600 / 1sec
43079
R/W
Aux. DO3 Relay Type
UINT16
Refer to “Value Table T12”
43080
R/W
Aux. DO3 Dwell Time
UINT16
1 - 600 / 1sec
43081
R/W
Aux. DO4 Relay Type
UINT16
Refer to “Value Table T12”
43082
R/W
Aux. DO4 Dwell Time
UINT16
1 - 600 / 1sec
43083
R/W
Aux. DO5 Relay Type
UINT16
Refer to “Value Table T12”
43084
R/W
Aux. DO5 Dwell Time
UINT16
1 - 600 / 1sec
43085
R/W
Aux. DO6 Relay Type
UINT16
Refer to “Value Table T12”
43086
R/W
Aux. DO6 Dwell Time
UINT16
1 - 600 / 1sec
43087
R/W
Aux. DO7 Relay Type
UINT16
Refer to “Value Table T12”
43088
R/W
Aux. DO7 Dwell Time
UINT16
1 - 600 / 1sec
43089
R/W
Aux. DO8 Relay Type
UINT16
Refer to
“Value Table T12”
43090
R/W
Aux. DO8 Dwell Time
UINT16
1 - 600 / 1sec
43091
R/W
Aux. DO9 Relay Type
UINT16
Refer to “Value Table T12”
43092
R/W
Aux. DO9 Dwell Time
UINT16
1 - 600 / 1sec
43093
R/W
Aux. DO10 Relay Type
UINT16
Refer to “Value Table T12”
43094
R/W
Aux. DO10 Dwell Time
UINT16
1 - 600 / 1sec
43095
R/W
Digital Output Save Request
(Save Address : 43071 - 43094)
UINT16
0x00FF = Save Request
0x0000 = Do Not Save
•••
Invalid
UINT16
•••
43100
Invalid
UINT16
Содержание ACCURA 7500
Страница 6: ...Page 6 Standard Compliance Process Control Equipment E324900...