EN
59
11.4
Voltage menu at output load - CONSULTATION ONLY
The indicated data is only indicative
EXAMPLE OF CONTROL UNIT POWERED BY BATTERY
36.5V
24.3V
24.3V
21.7°C
OUT1
OUT2
VREG
OUT1
indicates the voltage that the battery supplies
to the control unit on output OUT1.
OUT2
indicates the voltage that the battery supplies
to the control unit on output OUT2. If less than
24V it means that too many accessories are
connected to the 24V output of the control
nit (overload).
NOTE
: OUT2 is not visualised in the case of
installation for a 24V control unit
(visualisation of OUT2 ----)
VREG
indicates the voltage used by the internal
voltage regulator
WARNING!!!
If the battery is delivering current and is discharged, the OUT1 and OUT2 outputs are disabled and "
----
" is displayed.
If the battery is delivering current and you are in the PowerSave time slot (par. 11.11),
PSAV
is displayed.
If "
RTM BATTERY LIFE
" is selected (par. 11.7) and the automation is turned on thanks to a command sent to B71/
PBX/RTCC, it displays
BTLO
(indicating that the batteries are low, and after this activation it will turn off the control
unit again)
EXAMPLE OF A CONTROL UNIT POWERED BY MAINS VOLTAGE
SEC1
SEC2
50.0HZ
21.7°C
OUT1
OUT2
FREQ
˜
˜
The
OUT1
output supplies the ~ SEC1 voltage to the control
unit
The
OUT2
output supplies the ~ SEC2 voltage to the control
unit
NOTE
: OUT2 is not visualised in the case of installation for a
24V control unit (visualisation
of OUT2 ----)FREQ indicates the network frequency detected.
11.4.1
Examples of error alerts / alarms - Charge and output load regulator menu
ERROR ALERT/ALARM
DESCRIPTION
ON
Battery electrically connected to the outputs
OUT1
and
OUT2
.
The control unit is powered by battery
The battery is disconnected from the output
OUT1
and
OUT2
.
The control unit is powered by the
SEC1
,
SEC2
voltage or it is NOT powered
(activation of the safeguard mode for "low battery").
ALARM
DESCRIPTION
V
Excessively high voltage detected on the internal voltage regulator (V)
V
Excessively low voltage detected on the internal voltage regulator (V)
Detected temperature too high for correct operation. When the maximum
temperature (+55°C) is exceeded, battery charging is deactivated and will
not start again until the temperature falls to 50°
Detected temperature too low for correct operation. When the temperature
falls below -25°C, battery charging is deactivated and will not start again
until the temperature rises to -20°
OFFSET error. Error in in charge control circuit calibration.
NOTE:
the OFFSET alarm is critical and inhibits the automatic reset of the
battery charger functions. Contact Customer Service.
Temperature in the box
Temperature in the box